INFORMATION ON CASE DAC08-00054
Status :  
Name :  
Address :  
Application Date :  
Parcel :  
REC 
MOHAMAD S ALBAGHDADI 
16 COLWYN CT  (click for map) 
6/19/2008 10:37:26 AM 
1004177003  (click for parcel details)
Description :

ACTIVITIES
Insp - Perm Electrical Service
Staff : PFH  Status : PASS  Date1 : 11/21/2008  Date2 : 11/21/2008  Date : 11/21/2008 
Notes :
UNIT 16
New Feeder cables have been installed and metering equipement was not contaminated by the flood water. (Breakers) Have been Installed. 
Insp - Perm Electrical Service
Staff : PFH  Status : FAIL  Date1 : 11/19/2008  Date2 : 11/19/2008  Date : 11/19/2008 
Notes :
FAIL
1. Main Breakers for units #18 and #12 will need to be installled to protect the energized parts inside of the Main Switchgear. (OR LOCKED OUT)
2. Need to verify that the feeder cables to the unit were not contaminated by the flood water and if they were they will need to be replaced.
3. Properly terminate the cable hanging from the back garage wall.
4. Temporary receptacles installed for construction and repair purposes will need to GFCI protected. 
Insp - Perm Electrical Service
Staff : PFH  Status : FAIL  Date1 : 10/31/2008  Date2 : 10/31/2008  Date : 10/31/2008 
Notes :
1. WILL NEED TO HAVE THE LICENSED ELECTRICIAN OBTAIN A ELECTRICAL PERMIT FOR THE ELECTRICAL WORK THAT HAS ALREADY BEEN COMPLETED.
2. IF THE ELECTRICIAN IS NOT LICENSED BY THE STATE OF IOWA OR BY THE CITY OF IOWA CITY WE WILL NEED TO MEET WITH OWNER OF THE PROPERTY, THE ELECTRICIAN THAT PERFORMED THE WORK, AND THE LICENSED ELECTRICIAN THAT WILL BE OBTAINING THE ELECTRICAL PERMIT FOR THE REPAIR.
3. WILL NEED TO REMOVE ALL CABLES, BOXES, AND DEVICES THAT HAVE BEEN CONTANMINATED BY THE FLOOD WATER.
4. NEED TO MAINTAIN 1-HOUR CONSTRUCTION OF THE PARTYWALLS BETWEEN THE UNITS. (AT THE ELECTRICAL PANEL ETC.)
5. CAN NOT OCCUPY DWELLING UNTIL FINAL INSPECTION HAS BEEN COMPLETED.
6. ALL ELECTRICAL WORK WILL NOT BE ALLOWED TO CONTINUE UNTIL A ELECTRICAL PERMIT HAS BEEN OBTAINED BY A MASTER STATE OR MASTER IOWA CITY LICENSED ELECTRICAN, AND PROOF OF INSURANCE LISTING THE CITY OF IOWA CITY AS AN ADDITIONAL INSURED; SUBMITTED TO THE IOWA CITY BUILDING DEPARTMENT. 
Insp - Gas Pressure Test
Staff : BFO  Status : PASS  Date1 : 9/22/2008  Date2 : 9/23/2008  Date : 9/22/2008 
Insp - Gas Meter Release
Staff : BFO  Status : DONE  Date1 : 9/22/2008  Date2 : 9/23/2008  Date : 9/22/2008 
Notes :
released to Mid-american 