| INFORMATION ON CASE DAC08-00057 | ||
|
Status : Name : Address : Application Date : Parcel : |
REC JESSICA LYNN MCALLISTER 24 COLWYN CT (click for map) 6/19/2008 10:40:38 AM  1004177006 (click for parcel details) |
Description : |
| ACTIVITIES | ||||
| Insp - Perm Electrical Service | ||||
| Staff : PFH  | Status : FAIL  | Date1 : 10/31/2008  | Date2 : 10/31/2008  | Date : 10/31/2008  |
| Notes : UNITS OF BUILDING 22 - 24 - 26 - 28 & HOUSE PANEL THESE CAN NOT BE RELEASED FOR THE FOLLOWING REASONS. 1. LOWER LEFT HAND SERVICE BREAKER AND METER SOCKET WAS CONTAMINATED AND NEEDS TO BE REPLACED BEFORE THAT UNIT CAN BE ENERGIZED. 2. ALL OF THE INSIDE OF THE ENCLOSURES NEED TO BE CLEANED OUT WITH DE-NATURED ALCOHOL, AND ANTIBACTERIAL SOLVENT. 3. ALL METER SOCKETS / SERVICE BREAKERS WILL NEED TO BE PROPERLY LABLED. 4. ALL FEEDER CABLES ARE FINE AND DO NOT NEED TO BE REPLACED. A CABLE TYPE CONDUCTOR WAS USED NAD IT IS RATED FOR DIRECT BURIAL CONDITIONS.  |
||||