Loading...
HomeMy WebLinkAbout7/1/02 350 DublinFARRIS ENGINEERING CONSULTING ENGINEERS DESCRIPTION: 11239 CHICAGO CIRCLE 818 P STREET, SUITE 100 BY: DATE: FE NO. OMAHA, NEBRASKA 68154 LINCOLN, NEBRASKA 68508 402-330-5900 402-477-6163 CHKD: DATE: SHEET NO. OF 041251/071004 0112 F~RRIS ENG - MelroseRe~rementCommuni~ Unit Dimensions - Air-Cooled Condensing Units (Commercial) Item: F1 Qty: 1 Tag(s): CU-1 ELECTRICAL DATA TONS UNIT OPERATING VOLTAGE RANGE UNIT PRII~Y VOLTAGE UNIT ,~F_CONO~Y VOLTAGE UNIT HERTZ UNIT PHASE MINIMUM CIRCUIT AMPACITY (3) MAXIMUM OVERCURRENT PROTECTION DEVICE (2) RECOMMENDED DUAL ELEMENT FUSE (4) 60 211,2 180 - 220 200 6O 3 282 3OO 3OO kW COMPRESSOR NUMBER TONS (EA) COMPRESOR RATED LOAD AMPS (EA) LOCKED ROTOR AMPS (EA) kW 15 ,-- I%19 60.5 kW OUTDOOR MOTOR NUMBER 6 HORSEPOV~ER 1.0 MOTOR SPEED (RPM) 1'14~ OUTDOOR MOTOR FUlL LOAD AMPS 4.1 LOCKED ROTOR AMPS 20.7 kW Notes: 1. Elecl~ical dala is fo~ each individual motor. 2, Maximum overcurrent protection permitted by NEC 440-22 is 225 percent of largest coml~ressor motor RLA plus the remaining molto' RLA and FLA value,:. 3. Minimum circuit ampecity is 125 percent of ~ largest comixessor motor RI.A plus the remaining moto~ RLA and FLA values, 4. Recommended dual element fuse size is 150 percent of the largest cumpressor motor RLA plus the remaining moto~ RLA ~ FLA values, 5. Local codes may take precedence. TOTRL P,03