HomeMy WebLinkAbout7/1/02 350 DublinFARRIS ENGINEERING
CONSULTING ENGINEERS DESCRIPTION:
11239 CHICAGO CIRCLE 818 P STREET, SUITE 100 BY: DATE: FE NO.
OMAHA, NEBRASKA 68154 LINCOLN, NEBRASKA 68508
402-330-5900 402-477-6163 CHKD: DATE: SHEET NO. OF
041251/071004 0112
F~RRIS ENG
- MelroseRe~rementCommuni~
Unit Dimensions - Air-Cooled Condensing Units (Commercial)
Item: F1 Qty: 1 Tag(s): CU-1
ELECTRICAL DATA
TONS
UNIT OPERATING VOLTAGE RANGE
UNIT PRII~Y VOLTAGE
UNIT ,~F_CONO~Y VOLTAGE
UNIT HERTZ
UNIT PHASE
MINIMUM CIRCUIT AMPACITY (3)
MAXIMUM OVERCURRENT PROTECTION DEVICE (2)
RECOMMENDED DUAL ELEMENT FUSE (4)
60 211,2
180 - 220
200
6O
3
282
3OO
3OO
kW
COMPRESSOR
NUMBER
TONS (EA)
COMPRESOR RATED LOAD AMPS (EA)
LOCKED ROTOR AMPS (EA)
kW
15 ,-- I%19
60.5
kW
OUTDOOR MOTOR
NUMBER 6
HORSEPOV~ER 1.0
MOTOR SPEED (RPM) 1'14~
OUTDOOR MOTOR FUlL LOAD AMPS 4.1
LOCKED ROTOR AMPS 20.7
kW
Notes:
1. Elecl~ical dala is fo~ each individual motor.
2, Maximum overcurrent protection permitted by NEC 440-22 is 225 percent of largest coml~ressor motor RLA plus the remaining molto' RLA and FLA value,:.
3. Minimum circuit ampecity is 125 percent of ~ largest comixessor motor RI.A plus the remaining moto~ RLA and FLA values,
4. Recommended dual element fuse size is 150 percent of the largest cumpressor motor RLA plus the remaining moto~ RLA ~ FLA values,
5. Local codes may take precedence.
TOTRL P,03