HomeMy WebLinkAbout1/21/14 reviewpepperjax January 10, 2014 Terry Goerdt RE: Project Name: Pepperjax Grill Iowa City Schnackel Project No.: 131084 Dear Terry: This letter is in response to plan review comments dated January Electrical Review Item 1 … Sheet E1.1 - Exit light required for rear exit. Exit sign has been added to the rear exit. Item 2 … Sheet E3.1 - Please verify permitted calculate load for Power Panel M. Calculated power is accurate, 220.88 is stated to be an optional calculation intended to avoid over sizing the service, plans comply with 220.56 which allows a 65% demand factor for kitchen equipment. Item 3 … Sheet E3.1 … Prints show 300 amp fuses for main disconnect. See response to item 2 Item 4 … Sheet E3.1 … Verify total connected load with NEC 2011 Article 220.88 Table 220.88. See response to item 2 Item 5 … Sheet E3.1 … 80% load of 155.8 KVA connect load = 124640 / by 36 amps. See response to item 2 Item 6 … Sheet E3.1 … Print calls for 300 amp fuses. See response to item 2 Schnackel Engineers, Inc. 3035 South 72nd Street Omaha, Nebraska 68124 Phone: 402-391-7680Fax: 800-930-9526Toll Free: 1-800-581-0963www.schnackel.com Project Name: Error! Reference source not found. Schnackel P Error! Reference source not found. Page 2 Item 7 … Sheet E3.1 … 350 MCM wire copper is rated for 310 amps. See response to item 2 If you have any questions, please let me know. Sincerely, Tyler Hopson, Electrical Engineer cc: Schnackel Engineers, Inc. 3035 South 72nd Street Omaha, Nebraska 68124 Phone: 402-391-7680Fax: 800-930-9526Toll Free: 1-800-581-0963www.schnackel.com