HomeMy WebLinkAbout11/5/15 planssolar2015
112 E. WASHINGTON STREET
ICE CREAM ROOF
WHITEYS
PANEL AND INVERTER TO BE CERTIFIED TO UL1703, UL 1741/IEEE
INVERTERS: (14) SIEMENS SMINT215R60MC (ENPHASE IS EQUAL)
MECHANISM THAT SHUTS DOWN THE INVERTER AND MEETS THE
OF THIS INVERTER IS ON THE PANEL AND THE LOW VOLTAGE DC
THE REQUIREMENT OF NEC SECTION 690.91. THE INSTALLATION
IS ISOLATED INSIDE THE PV MODULE THUS MEETING ITEM 2 OF
THE MICROINVERTER INCORPORATES AN INTERNAL CONTROL
RAPID SHUT-DOWN REQUIRMENT OF NEC SECTION 690.12 AND
THAT MEETS THE REQUIRMENTS OF NEC SECTION 590.56(C).
THE PV MODULES WILL BE LABELED OR SIGNAGE PROVIDED
1547, CSA 22.2 NO. 0-M91, 0.4-04, AND 107.1-01.
ELECTRICAL GENERAL NOTES:
(14) HYUNDAI 260W
SYSTEM SIZE: 3.64 kWdc
NEC SECTION 690.12.
PANELS:
DC LEADS FROM
MI TO PANEL.
BY INVERTER MFR.
BY INVERTER MFR.
CONDUIT SERVES AS EGC.
COPPER, THWN-2, IN 1/2" C .
4# 10 (3 PHASE & 1 NEUTRAL)
TRUNK CABLE
TRUNK CABLE
PV PANEL
MIMIMIMIMIMIMI
PV PANEL
MIMIMIMIMIMIMI
TYPICAL ALL PANELS
RACKING BONDED
PLUG CONNECTIONFROM MI TO TRUNK
PANELS AND
TO EGC.
#6 CU
CABLE