HomeMy WebLinkAbout05-18-2015 Board of AppealsCITY OF 10__WA_ CITY_
NOTICE OF PUBLIC MEETING
The Iowa City Board of Appeals will convene at 4:00 p.m. on Monday May 18,
2015 in Emma J. Harvat Hall 410 Washington St., Iowa City, Iowa
TENTATIVE AGENDA
1. Meeting to be called to order
2. Elect Officers for 2015 (Chair and Vice Chair)
3. Consider the minutes from the March 24, 2014 meeting.
4. Discussion and possible recommendation to Council regarding the
adoption of the 2015 International Building and Fire Codes.
5. Discussion and possible recommendation to Council regarding
amending the Licensing Code.
6. Adjournment
MINUTES
IOWA CITY BOARD OF APPEALS
MONDAY, March 24, 2014
HELLING CONFERENCE ROOM, CITY HALL
410 E. WASHINGTON STREET
IOWA CITY, IA 52240
MEMBERS PRESENT: John Roffman, Scott McDonough, Andrea French, John Gay
MEMBERS ABSENT: None
STAFF PRESENT: Tim Hennes (Sr. Building Inspector), Sue Oulek (Asst. City
Attorney), Brian Greer (Fire Marshall), Julie Tallman (Development
Regulations Specialist acting as minute taker), Doug Boothroy (Director,
Neighborhood and Development Services), Dave Campbell (Building Inspector)
OTHERS PRESENT: Marty Christiansen and Dan Ouverson
RECOMMENDATIONS TO COUNCIL
Recommended by a unanimous vote (4-0) to proceed with the adoption of the proposed amendments to
the 2009 International Mechanical Code that reflect the changes to commercial hood exhaust systems.
CALL TO ORDER:
John Roffman called the meeting to order at 4:00 PM
ELECTION OF OFFICERS:
French moved to elect John Roffman as chairperson of the Board of Appeals. McDonough seconded.
VOTE: Roffman was elected as chairperson of the BOA by a 4-0 unanimous vote.
McDonough moved to elect Andrea French as vice -chair of the Board of Appeals. Gay seconded.
VOTE: French was elected vice -chair of the BOA by a 4-0 unanimous vote.
CONSIDERATION OF MINUTES
Minutes from 11/4/2013 meeting were reviewed. McDonough moved to adopt the minutes. French
seconded. The minutes were approved by a unanimous 4-0 vote.
Appeal of the decision of the Building Official or Fire Chief— 120E Burlington St The Mill Restaurant
Appealing the decision of the building inspectors decision that raised seating was required to be
accessible to persons with disabilities per 2010 ADA Standards for Accessible Design.
Dulek suggested that the appellants' second point be argued first, because if the appellants are able to
prove one of the exceptions (accessibility is technically infeasible, or disproportionate relative to overall
cost of improvement) then Section 202 applies to the situation at hand, but this particular project is
exempt. If the appellants fail to prove that one of the two exceptions apply, then discussion will return to
appellants' first point, which is that the project is already in compliance with Section 202 and additional
modifications are not required. Dulek felt, and the Board and appellants agreed, that beginning with the
appellants' second point would be a more efficient use of time.
Appellant Christensen gave a history of the last ten years since he and Dan Ouverson purchased The Mill
as a mission to save an Iowa City live music venue. After nine years of operation, they had paid off the
debt one year ago. Christensen said investment in the building was difficult because the owner of the
building had not been willing to sign a lease for the last six years; however, when their debt was paid off,
Christensen and Ouverson decided to invest in the front and back sections of The Mill over the lull of
winter break. The improvement projects included raising some of the booths in the back section to
improve patrons' visibility of performers on stage.
Seven booths were raised on two tiers of platforms: one tier was elevated 7" and the second was elevated
14". Christensen pointed out that the vast majority of seating was accessible, with the exception of three
booths.
Christensen said that building staff had prepared a plan showing how ramps could be incorporated into the
design of the raised platforms and seating, so the test of "technically infeasible" could not be met;
however, Christensen maintained that the ramps and their attendant handrails would have a negative
impact on circulation forwait staff and patrons, and in any event where the venue needed to be exited in
an emergency. Christensen also expressed his opinion that "circulation path" was not clearly defined in
Section 202, and that there was a clear circulation path around the interior of the seating area except for
three out of the seven booths.
Hennes reviewed Section 202.4 "alterations" and the issue of disproportionality. He explained that the
figure $20,000 was provided by Ouverson, so appellant had to prove that the cost of the ramps and
handrails would exceed 20%, or $4,000. Hennes illustrated how building staff arrived at a means to
provide an accessible route to both platforms without losing any of the seating that appellants had
provided. Using the design showing full accessibility, then, appellant had to show whether cost of
construction for the ramps exceeded $4,000.
McDonough asked if making both raised platforms accessible would essentially provide an advantage to
disabled persons. Christensen pointed out that preferred seating is usually closest to the stage, so
persons with disabilities were already afforded preferred seating.
Hennes returned the discussion to clarifying the definitions of technical infeasibility and disproportionality,
and their applicability to appellants' appeal. Technical feasibility is, by definition, when structural changes
are necessary to achieve accessibility — for instance, removing walls. Structural changes were not
required in this instance so technical feasibility was not a proven exception. Disproportionality had not
been proven because appellants had not provided proof that the ramps would cost more than $4,000.
Hennes also pointed out that even if disproportionality was proven, then up to $4,000 would still have to be
spent on accessibility improvements as part of the project.
Hennes then provided some background on the progression of the project and that, while a building permit
was required for the construction of the elevated platforms, no building permit was secured and that staff
found out about the project from a Facebook posting. Hennes also noted that when staff notified
appellants that the project required a building permit, they promptly came to the building department and
secured a building permit.
Roffman inquired if there was any language in Section 202 that would suggest that a ramp is not required;
i.e., that accessibility was not a required element of the design for 7 booths on two raised platforms.
McDonough noted that this was the discussion that would follow after consideration of whether the project
met one of two exceptions: technical infeasibility, or disproportionality.
Dulek and Hennes posed the question to BOA: "Does the Board agree that the ramps are either
technically infeasible or disproportionate in cost?"
McDonough's opinion was that at least a part of the ramp design prepared by building staff could be done
for $4,000 or less, and that the design was technically feasible.
Roffman noted that if this was a sports venue, the existing configuration would be acceptable
McDonough stated that similar to a sports arena, visibility is assured for disabled patrons because
accessible seating is on the floor.
Christensen said that "dining area' is not clearly defined in Section 202 and the code instructs us to refer
to a collegiate dictionary definitions.
Hennes stated that if this is a dining area and had we reviewed the plan prior to issuing a building permit,
we would have concluded that the appellants' points 1, 2, and 3 are not applicable; i.e., that accessibility to
the raised platforms would be required.
Christensen replied that the entire room is a dining area, and it is largely accessible.
McDonough asked why the raised seating was not considered a mezzanine, and exempt from
accessibility.
Hennes replied that the platforms aren't mezzanines because there is not 7 feet between them and the
next lowest floor.
Dulek explained that Section 202 refers specifically to "all dining areas — including raised or sunken
seating and outdoor dining areas."
Gay asked if the two platforms weren't really one raised dining area and if access tb one of the two
platforms would comply with Section 202.
Roffman wondered if that was acceptable to the appellants. By providing ramp access to one of two
platforms, they would not have the degree of construction from handrails and ramps that they would have
from providing access to both platforms.
Christensen wondered what exactly constituted a "dining area. He believed the entire 24 x 24 room is one
dining area and it is 80% accessible.
French stated that by code, an "altered area" such as the new raised platforms, carried with it specific
requirements in Section 202.
Christensen stated that the back of The Mill is almost like a dinner theatre more than a dining area. It's
used for events, parties, performances. If it was called an assembly use, there would be exceptions to
accessibility for fixed seating. The booths are fixed seating.
Hennes said that if Section 221 applies, the code issues become more specific and require preferential
seating to be accessible. The raised platforms were installed to improve line of sight, and would be
considered preferential seating.
Christensen replied that the best line of sight is from the floor where it's fully accessible. (He then
distributed an email that The Mill had received, expressing appreciation for the venue's accessibility from a
person with disabilities).
Roffman said that the crux of the matter seems to be whether this is a dining area and asked the Board
members if they agreed. Mcdonough said yes.
Ouverson stated that the Mill is not your typical place - there's no other venue that would struggle with the
obstacles we do because of space.
Hennes explained that code cannot be enforced that way— also, that there was the option of enforcing the
IBC in place of the ADAAG, and IBC does give us interpretations on some of these issues.. The IBC states
a dining area is a "special occupancy." Section 1108.2.9 of the 2009 IBC explains the applicability of
accessibility to dining areas — the commentary says "raised areas are required to be accessible" and
therefore, accessible routes are required, especially in "special areas" (i.e,, dining rooms).
Roffman stated that they were back to appellants' point one, whether accessibility is required, and the
conclusion appears to be that accessibility is, indeed, required.
Hennes said that he thought Gay's solution seemed reasonable, providing access to raised seating on one
of two adjacent platforms.
MOTION: McDonough motioned that the elevated seating is required to be accessible and access to the 7
inch raised platform meets the accessibility requirement. Gay seconded.
VOTE: The motion passed 4-0.
Christensen thanked staff for their consideration, and noted his gratitude for the opportunity to participate
in a democratic process.
Amendments to 2009 Mechanical Code for Type I and II exhaust fans in commercial kitchens
Hennes distributed a memo regarding the history of concerns over noise emanating from grease exhaust
fans when restaurants were adjacent to residential uses. He clarified that the new code language would
apply to changes in use; changes in occupancy; and new construction.
Roffman asked about buildings downtown where finding the route for a chase to exhaust through the roof
could prove near impossible.
Hennes said that alley access was allowed in the amendments
Boothroy explained that Historic Preservation Commission and the Planning & Zoning Commission asked
staff to look into the issue, both from the perspective of using noise measurement to determine whether an
exhaust was a nuisance, and from the perspective of regulating new construction in a way that future
exhaust chases could be designed into buildings where tenancy might be open to a future restaurant. It
was staffs conclusion that measuring decibels was less preferred; that controlling the impacts of
commercial exhaust was better achieved by regulating location than by reacting to an exhaust fan after it's
installed.
Hennes stated that replacing existing mechanical exhaust for commercial equipment can utilize existing
termination locations. There could be instances where newly -installed equipment can't utilize an existing
termination, in which case they would have to terminate through the roof or into an alley.
MOTION: McDonough moved that the proposed amendments to the 2009 International Mechanical Code
be recommended to City Council. French seconded.
VOTE: The motion was approved with a unanimous vote 4-0.
Neighborhood and Development Services
Boothroy introduced the BOA to the new staff organization at City Hall, under the heading of
Neighborhood and Development Services. He explained that the new structure does not affect staff
support of the Board of Appeals and that support would still be provided by the building inspection staff
He clarified that Planning and Building staff would be combined under the heading of Development
Services.
There were no questions.
Roffman adjourned the meeting at 5:40.
OTHER BUSINESS:
None.
Date
CITY OF IOWA CITY
MEMORANDUM
Date: May 13, 2015
To: Iowa City Board of Appeals
From: Tim Hennes, Senior Building Inspector
Re: Notable Changes Contained in the 2015 Edition of Building Codes.
Following are significant changes made by local amendments and notable changes between
the 2009 codes and the 2015 codes.
1. International Residential Code (IRC) (Local Amendments)
The majority of amendments of the IRC are for clarification of a code requirement or to
reflect local practices that have evolved from previous building codes and their
amendments.
Following are notable changes or proposed new amendments:
Section R105.2: Revised the exceptions that excluded structures in a Historic
Preservation Overlay Zones and Iowa City Historic Landmarks from requiring a building
permit to replace roofs and street facing exterior doors.
Comment: This change will reciui a «';uilc!i-ig Dern nit to mpiace a street 7acinc,
door anc 'Co raroof a stfuci:ure iri Historic Preservation Overlay zones and on Iowa
City Historic Landmarks. Structures located in Historic Conservation Zones are not
affected.
These changes will assure the new material is reviewed according to the Iowa City
Historic Preservation Guidelines.
Section R302.5.1: Delete the requirement that requires house to garage doors to have
self-closing devices.
Comment: This amendment was deleted in previous code cycles and now has been
reinstated. The amendment to delete the requirement maintains current requirements.
The amendment does not prohibit someone from installing such device.
Section R302.13: Delete the requirement to protect the underside of floor/ceiling
assemblies in unfinished basements.
Comment: This amendment eliminates the requirement to drywall the ceiling or sprinkle
an unfinished basement ceiling. The amendment does not prohibit someone from
installing such protection.
Section R304.1: Revise the minimum 70 square feet required for habitable room size
and to 120 square feet.
Comment: the amendment increases the minimum square feet required for a habitable
room from 70 square feet to 120 square feet. The amendment provides consistency
with the Iowa City Housing Code and is unchanged from previous building code
adoptions.
Section R312.2 (IRC) & 1015.8 (IBC): Delete the requirement to install guards on
operable windows that are located less than 24" above the floor and more than 72"
above the finish surface on the exterior of the building.
Comment: The amendment eliminates the requirement to install guards on all operable
windows that meet specified location criteria. The requirement is not consistent with
other guard location criteria requirements and could conflict with emergency and
escape window opening requirements. This amendment does not prohibit the
installation of fall protection devices on windows.
Section R313: Delete the requirement to install a fire sprinkling system in one- and
two-family dwelling and townhouses.
Comment: This amendment eliminates the requirement for structures regulated by the
IRC have an automatic fire suppression system installed. The amendment does not
prohibit the installation of a automatic fire suppression system.
Section R320.2: Add eight provisions to implement universal design features that
provide accessibility, usability and visit -ability for all.
Comment: The amendment applies only to new dwelling units and is not required for
existing structures for repairs, alterations, change of occupancy or additions unless the
square footage of the addition is more than 25% of the existing structure, then, the
addition must comply.
The minimum usability requirements are as follows:
1. Step -less Entrance: At least one entrance must be designed to provide a
step -less entry.
2. Interior doors: At least one bedroom and one bathroom, if either are provided,
and all other passage doorway header widths, on the level served by the
designed step -less entrance, must be framed to accommodate a minimum 38"
clear rough opening. The framing for the doorway width opening may be reduced
to accommodate any door size.
3. Sanitation facilities: There must be at least one bathroom containing a
water closet (toilet) and lavatory (sink) on the level of the dwelling to be
accessed by the designed step -less entrance. The room shall have a
minimum thirty inches (30") by forty-eight inches (48") clear floor space at the
water closet and lavatory.
4. Wall Reinforcement: A bathroom must be provided with wood blocking
installed within wall framing to support grab bars as needed.
5. Decks: All exterior decks and patios surfaces adjacent to the level served
by the designed step -less entrance must be built within four inches (4") of the
dwelling units finish floor level.
6. Switch and outlet re uirements: All wall switches, controlling light
fixtures, fans, a temperature control devices and all receptacles shall be
located in an area between fifteen (15) and forty-eight (48) inches above
finished floor.
7. Electrical panel requirements: : Electrical panels on the level of the dwelling
o e accessed y the designed step-less entrance shall be located so that
the individual circuit breakers are located between 15" and 54 " above the
floor.
8. Garages: Must be wired for power operated overhead doors.
Section R326: Delete Section R326 Swimming Pools, Spas and Hot Tubs.
Comment: This section was moved to the body of the code from the appendix. Deleting
it results in no change of enforcement for pools, spas and hot tubs. They are still
regulated by the electrical and zoning code.
Section 423.4 of the IBC; Adds a requirement to provide storm shelters in new
schools.
Comment: The 2015 IBC now specifically requires storm shelters for new schools. An
amendment is proposed to clarify the requirement is for new schools only and exempts
portable classrooms. The amendment also defers to the State of Iowa building code, if it
is more restrictive. The Iowa Department of Public Safety will be reviewing this code
provision in the near future. If the State adopts a more restrictive code requirement for
storm shelters in schools, this amendment will allow the Iowa City Building Code to be
consistent with state regulations. This will help to provide consistency with other
jurisdictions with regards to standards for this code provision.
Section R703.2: Adds a requirement to install water -resistive barrier on detached
accessory buildings.
Comment: The amendment requires a water-resistant barrier be applied on all
structures to protect from moisture in this climate.
Section IRC M1506.2 (IRC): Change limits exhaust duct lengths to table M1506.2.
Comment: In previous codes there was no limit to the length of exhausts ducts such as
bath fans. That has been addressed with this table.
Section G2415.3: Eliminates the requirement prohibiting gas piping not extend through
any townhouse unit other than the unit served by such gas piping.
Comment: Amendment is consistent with the mechanical and fuel gas code with regard
to gas piping being installed through dwelling units. Zero lot -line units will still be required
to have separate services but single structures that contain multiple units will be allowed
to have the gas piping extend through other units. This is consistent with how gas pipe is
installed now and in the past.
Appendix J (IRC): Existing Buildings and Structures:
Comment: The purpose of these provisions is to encourage the continued use or reuse
of legally existing buildings and structures. These provisions are intended to permit
work in existing buildings that is consistent with the purpose of this code.
2. Plumbing Code
a. Adopt by reference the State Plumbing Code:
Comment: Iowa Code Section 105.4 requires iocai jurisdictions to adopt the State Plumbing
Code by December 31$` 2016. The Iowa State Health Department, by law, adopts the
current edition of the Uniform Plumbing Code within six months of publication with a few
amendments. These amendments are consistent with the amendments that Iowa City
has had to the Uniform Plumbing Code over the past twenty years. The only exception
being that the City of Iowa City has had its own table for the numbers of required
plumbing fixtures in habitable structures. When this table was written into the Iowa City
Plumbing Code 25 years ago, additional plumbing fixtures were required in some
occupancy types to create "potty parity" between the sexes. These issues have been
addressed in the other plumbing codes subsequently. Adoption of the State Plumbing
Code will result in that slightly less number of plumbing fixtures will be required at low
occupant load levels and slightly more plumbing fixtures will be required at high
occupant load levels than are currently required by the Iowa City Plumbing Code fixture
tables.
3. Mechanical Code
a. Adopt by reference the State Mechanical Code:
Comment: Iowa Code Section 105.4 requires local jurisdictions to adopt the State Mechanical
Code by December 315` 2016. The Iowa State Department of Public Health, as administer
by the Plumbing and Mechanical Systems Board, adopts the current edition of the
International Mechanical Code within six months of publication with a few amendments.
cc: Doug Boothroy, Director, Neighborhood and Development Services
John Yapp, Coordinator, Development Services
Joan Tiemeyer, Executive Officer, The Greater Iowa City Area Home Builders Association
Prepared by: Tim Hennes, Sr. Building Inspector, 410 E. Washington St., Iowa City, IA 52240; 319-356-5122
ORDINANCE NO. 15 -
AN ORDINANCE AMENDING TITLE 17, CHAPTER 1, BUILDING CODE, BY ADOPTING THE
INTERNATIONAL BUILDING CODE, 2015 EDITION, INCLUDING APPENDIX K ADMINISTRATIVE
PROVISIONS, AND THE INTERNATIONAL RESIDENTIAL CODE, INCLUDING APPENDIX F RADON
CONTROL METHODS, AND APPENDIX J EXISTING BUILDINGS AND STRUCTURES, 2015
EDITION, PUBLISHED BY THE INTERNATIONAL CODE COUNCIL AND PROVIDING FOR
CERTAIN AMENDMENTS THEREOF; TO PROVIDE FOR THE PROTECTION OF THE HEALTH,
WELFARE AND SAFETY OF THE CITIZENS OF IOWA CITY, IOWA.
BE IT ORDAINED BY THE CITY COUNCIL OF THE CITY OF IOWA CITY, IOWA:
SECTION I. PURPOSE. The purpose of this ordinance is to adopt the 2015 Edition of the International Building
Code and International Residential Code as published by the International Code Council and to provide for certain
amendments thereof; and to provide for the protection of the health, welfare and safety of the citizens of Iowa City,
Iowa, and to provide for its enforcement.
SECTION Il. Sections 17-1, 17-2, 17-3 and 17-4 of the Iowa City Code are hereby repealed and the following
new Sections 17-1, 17-2, 17-3 and 17-4 are enacted in lieu thereof.
17-1-1: Code Adopted: Subject to the following amendments, the 2015 edition of the international building
code (IBC) and appendix K and the 2015 edition of the international residential code (IRC) including Appendix F,
radon control methods, and Appendix J, Existing Buildings And Structures are adopted. Additionally the Iowa State
Electrical Code, the Iowa State Mechanical Code, and the Iowa State Plumbing Code are hereby adopted.
Collectively they shall be known as the Iowa City building code or the building code. Interpretations of the building
official may be guided by publications of the international Code Council, Inc., or the International Existing Building
.Code.
17-1-2: Interpretation of Building Code peovisions: The provisions of this Code shall be held to be the
minimum requirements adopted for the protection of the health, safety and welfare of the citizens of Iowa City. Any
higher standards in the state statute or City ordinance shall be applicable.
17-1-3: Amendments to Code: The following sections of the 2015 edition of the international building code
and 2015 edition of the international residential code, are amended as follows:
Section 101.1 of both the h3C and IRC Delete Section 101.1 of both the IBC and IRC and insert in lieu thereof
the following:
101 1 Title These regulations shall be known as the Building Code of Iowa City, hereinafter referred to as
"this code."
Section 105.2 of both the IBC and IRC. Delete Section 105.2 of both the IBC and IRC and insert in lieu
thereof the following
105.2 Work Exempt from Permit. A permit shall not be required for the following:
Building
1. One-story detached accessory structures used as tool and storage sheds, playhouses and similar
uses, provided the floor area does not exceed 144 square feet provided the structure is not
located in a flood hazard area.
2. Fences not over 6 feet (1829 mm) high.
3. Oil derricks
4. Retaining walls which are not over 4 feet (1219 mm) in height measured from the bottom of the
footing to the top of the wall, unless supporting a surcharge or impounding Class I, II or IIIAliquids.
5. Water tanks supported directly on grade if the capacity does not exceed 5,000 gallons (18 925 L)
and the ratio of height to diameter or width does not exceed 2 to 1.
6. Sidewalks and driveways not more than 30 inches (762 mm) above grade and not over any
basement or story below and which are not part of an accessible route.
7. Painting, papering, tiling, carpeting, cabinets, counter tops and similar finish work.
8. Temporary motion picture, television and theater stage sets and scenery.
9. Prefabricated swimming pools which are less than 24 inches deep, do not exceed 5,000 gallons and
are installed entirely above ground.
10. Shade cloth structures constructed for nursery or agricultural purposes and not including service
systems.
11. Swings and other playground equipment accessory to detached one- and two-family dwellings.
12. Window awnings supported by an exterior wall which do not project more than 54 inches (1372
mm) from the exterior wall and do not require additional support.
13. Movable cases, counters and partitions not over 5 feet 9 inches (1753 mm) in height.
14. For structures regulated by the IRC the reapplication of shingles and roof sheathing provided:
a. Less than 50% of the structural sheathing is replaced and other structural alterations are not required.
b. The structure is not in a Historic Preservation Overlay Zone or is not an Iowa City Historic Landmark.
Note: Applying solid sheathing over space sheathing is not considered structural sheathing.
15. For structures regulated by the IRC reapplication of siding provided: The structure is not in a Historic
Preservation Overlay Zone, or a Conservation DistrictOverlay Zone, or is not an Iowa City Historic
Landmark. Street facing doors, all windows and all siding in any historic zone require a permit.
16. For structures regulated by the IRC replacing windows provided:
a. Replacement window(s) is in compliance with Appendix J.
b. The structure is not in a Historic Preservation Overlay Zone, or a Conservation DistrictOverlay Zone,
or is not an Iowa City Historic Landmark. All doors for an Iowa City Historic Landmark require a permit.
17. For structures regulated by the IRC replacing exterior doors, including garage doors, provided:
a. Replacement door(s) is in compliance with Appendix J.
b. t h e y r. r 3 n o t s t r e o t f a c i n q d o e r s i n structure located in a Historic Preservation
Overlay Zone or are not an Iowa City Historic Landmark.
Note: screen and storm doors do not require a permit re.3ard!L=t, & the location.
Electrical:
1. Portable motors or other portable appliances energized by means of a cord or cable having an
attachment plug end to be connected to an approved receptacle when that cord or cable is permitted by
this code.
2. Repair or replacement of fixed motors, transformers or fixed approved appliances of the same type
and rating in the same location.
3. Temporary decorative lighting.
4. Repair or replacement of current -carrying parts of any switch, contactor, control device or contact
device of the same type and/or rating.
5. Replacement of non -emergency over -current device of the required ampacity and interrupt rating
in the same location.
6. Repair or replacement of electrodes or transformers of the same size and capacity for signs or gas
tube systems.
7. Temporary wiring for experimental purposes in suitable experimental laboratories.
8. The wiring for temporary theater, motion picture or television stage sets.
Gas:
1. Portable heating, cooking or clothes drying appliances.
2. Replacement of any minor part that does not alter approval of equipment or make such equipment
unsafe
3 Portable -fuel -cell appliances that are not connected to a fixed piping system and are not
interconnected to a power grid.
Mechanical:
1. Portable heating appliances.
2. Portable ventilation appliances.
3. Portable cooling units.
4. Steam, hot- or chilled -water piping within any heating or cooling equipment regulated by this code.
5. Replacement of any minor part that does not alter approval of equipment or make such equipment
unsafe.
6. Portable evaporative coolers.
7. Self-contained refrigeration systems containing 10 pounds (4.54 kg) or less of refrigerant or that are
actuated by motors of 1 horsepower (746 W) or less.
8. Portable -fuel -cell appliances that are not connected to a fixed piping system and are not
interconnected to a power grid.
9. The replacement of fixed appliances provided however that the replacement appliance is in the same
location and has a rating equal to or less than the appliance being replaced, and it is not necessary to
remove, replace, alter, or install any additional ductwork or piping.
Plumbing:
1. The stopping of leaks in drains, water, soil, waste or vent pipe; provided, however, that if any
concealed trap, drainpipe, water, soil, waste or vent pipe becomes defective and it becomes necessary
to remove and replace the same with new material, such work shall be considered as new work and
a permit shall be obtained and inspection made as provided in this code.
2. The clearing of stoppages or the repairing of leaks in pipes, valves or fixtures, and the removal and
reinstallation of water closets, provided such repairs do not involve or require the replacement or
rearrangement of valves, pipes or fixtures.
3. The replacement or removal and reinstallation of any fixture or appliance, provided, however, that the
fixture or appliance is installed at the same location and it is not necessary to remove, replace, alter, or
install any piping. Exemption from the permit requirements of this Code shall not be deemed to grant
authorization for any work to be done in violation of the provisions of the Code or any other laws or
ordinances of this jurisdiction.
Exemption from the permit requirements of this Code shall not be deemed to grant authorization for any work to
be done in a manner in violation of the provisions of this Code or any other laws or ordinances of this
jurisdiction.
Section 105.5 of both the IBC and IRC. Modify Section 105.5 of both the IBC and IRC by adding a sentence
to the end as follows:
In no case shall the permit be effective unless the work covered by the permit has a documented
inspection every 6 months minimum and is completed within 24 months of the date on which the
original permit was issued.
Section 105.8 of the IBC and R106.10 of the IRC. Add two new Sections 105.8 and 105.8.1 to the IBC
and R105.10 and R105.10.1 to the IRC as follows:
105.8(IBC) R105.10(IRC) Demolition permits required. A demolition permit shall be required as follows:
1. For the removal of any building or structure.
2. For the removal of any portion of a building (I.e. porch, porch railing, decorative brackets and trim,
dormers, chimneys, etc.) that is located within a Historic Preservation Overlay Zone or a
Conservation District Overlay Zorie, or is an Iowa City Historic Landmark.
105.8.1 (IBC) and R105.10.1 Requirements. The applicant for any demolition permit shall state on
the application the proposed disposal plans for all demolition materials. No demolition permit shall be
issued until seven (7) working days after the date an application has been properly fled and said
demolition permit shall not be effective until applicant has posted the premises to be demolished with a
notice to be provided by the City and as directed by the City; provided, however, that accessory
buildings as defined in the Iowa City Zoning Ordinance and and dangerous buildings shall be exempt
from said notice and waiting requirement
Section 105.9 of the IBC and R105.11 of the IRC. Add two new Sections 105.9 to the IBC and R105.11 to
the IRC as follows:
105.9 (IBC) and R105.11 (IRC) Permittee:
1. An electrical, plumbing or mechanical permit may be issued to any person holding a valid master
license for the respective trade as described in Section 17-11-1 E of the Iowa City Code, or to any
company who employs a duly licensed master in the respective trade on a full-time basis who supervises
the work of the apprentice and or journeymen dunng the company's normal business hours.
2 An electrical, plumbing or mechanical permit may be issued to the owner of an existing owner -
occupied single-family dwelling, pursuant to a valid certificate of occupancy and used exclusively for
residential purposes, to do any electrical work in connection with said dwelling and accessory buildings.
The owner must personally purchase all material and perform all labor in connection with the permit.
Applicants for a homeowner's electrical permit shall pass the designated exam before a permit may be
issued.
3. The homeowner's test required in subsection 2 of this section may be waived if the applicant is a
duly licensed electrician with a minimum of a journeyman status.
Section 105.10 of the IBC and R105.12 of the IRC. Add two new Sections 105.10 to the IBC and R105.12
to the IRC as follows:
105.10 (IBC) and R105.12 (IRC) Insurance:
Before any permit to perform electrical or plumbing work may be issued, the applicant shall have on file with
the building official a copy of a certificate of insurance stating the liability amounts of no less than three
hundred thousand dollars ($300,000.00) property damage and five hundred thousand dollars ($500,000.00)
bodily injury. The city shall be named as additional insured. The policy shall also provide for at least ten (10)
days' notice by the insurer to the city of termination of the policy by the insured or insurer. Electrical permits
issued under sections 105.9 (IBC) and R105.11 (ICR) 2 and 3 shall be exempted from this insurance
requirement.
Section R107.3 of the IRC and Section 108.3 of the IBC. Amend Section R107.3 of the IRC and Section
108.3 of the IBC as follows:
R107.3 (IRC) 108.3 (IBC) Temporary Power: Replace the "NFPA 70" with "Iowa State Electrical Code.".
Section R108.2 of the IRC and Section 109.2 of the IBC. Delete Section R108.2 of the IRC and Section 109.2
of the IBC and insert in lieu thereof the following:
R108.2 (IRC) 109.2 (IBC) Permit Fees and Valuations. The fee for any permit shall be as set forth in the
permit fee schedule as established by resolution of the City Council. The determination of value or
valuation under any of the provisions of this Code shall be made by the Building Oficial. The value to
be used in computing the building permit and building plan review fees shall be the total value of all
construction work for which the permit is issued, as well as all finish work, painting, roofing, site grading,
paving, landscaping, elevators, and other permanent equipment. The value to be used in computing
the value of construction for reports shall be the total value of all construction work for which the
permit is issued, as well as all finish work, painting, roofing, electrical, plumbing, heating, air
conditioning, site grading, paving, landscaping, elevators, fire extinguisher systems and other permanent
equipment.
Section R108.3 of the IRC and Section 109.3 of the IBC. Delete Section R108.3 of the IRC and Section 109.3 of
the IBC and insert in lieu thereof the following:
R108.3 (IRC) 109.3 (IBC) Plan Review Fees. When a plan or other data are required to be submitted
by Section 106 and the value of the proposed building or work exceeds fifteen thousand dollars
($15,000), a plan review fee shall be paid before the permit may be issued. Should the project be
abandoned and the permit not issued after the plan review has been started, the plan review fee shall
still be due and payable. The plan review fee shall be as set forth by resolution of City Council. Plan
review fees are separate fees from the permit fee specified in Section R108.2 and 109.2 and are in
addition to permit fees.
Section R108. 5 of the IRC and Section 109.6 of the IBC: Delete Section R108.5 in the IRC and Section
109.6 of the IBC and insert in lieu thereof the following
R108.5 (IRC) 109.6 IBC Refunds: The Building Official may authorize the refunding of any fee paid
hereunder which was erroneously paid or collected The Building Official shall not authorize the
refunding of any fee paid except upon written application filed by the original permittee within one
hundred eighty (180) days from the date of fee payment.
Section R108.6 of the IRC and Section 109.4 of the IBC Delete Section 108.6 of the IRC and Section
109.4 of the IBC and insert in lieu thereof the following:
R108.6 (IRC) 109.4 (IBC) Work commencing before permit issuance: Any person who
commences work on a building, structure, electrical, gas, mechanical or plumbing system before
obtaining the necessary permits shall be subject to a fee equal to the amount of the permit fee if a
permit were issued This fee shall be collected whether or not a permit is issued. The payment of
such fee shall not exempt any person from compliance with all other provisions of this Code or
from any penalty prescribed by law Only the Building Official may reduce this fee when it is
demonstrated that an emergency existed that required the work to be done without a permit.
Section R112 of the IRC and Section 113 of the IBC. Delete Section R112 of the IRC and Section 113 of the
IBC and insert in lieu thereof the following:
Section R112 of the IRC and Section 113 of the IBC Appeals: See Title 17 Chapter 12 Appeals in the City
Code.
Section 202 of both the IBC and IRC. Add new definition as follows:
Authority Having Jurisdiction. The organization, office, or
individual responsible for approving equipment, materials, an
installation, or a procedure.
Section 202 of both the IBC and IRC. Add new definition as follows:
Chief Electrical Inspector. A building inspector who either is the authority having jurisdiction or is
designated by the authority having jurisdiction and is responsible for administering the requirements of this
code.
Section 202 of both the IBC and IRC. Add new definition as follows:
Electrical Inspector. A building inspector authorized to perform electrical inspections.
Section 202 of both the IBC and IRC. Add new definition as follows:
Family: See Title 14 Chapter 9 Article A Zoning Definitions in the
City Code.
Section 202 of both the IBC and IRC. Add new definition as follows:
Emergency Communications Center. Shall mean the Johnson County Emergency Communications
Center.
Section 202 of the IBC and IRC. Modify definitions as follows:
Habitable space: Add a sentence to the end of the definition of habitable space or room to read as follows:
Basement areas finished to a degree to encourage their use as anything other than storage or mechanical
rooms shall be considered habitable space.
Section R202 of the IRC. Delete definition of Accessory Structure and insert in lieu thereof the
following: ACCESSORY STRUCTURE. See Title 14 Chapter 9 Article A Zoning Definitions in
the City Code.
Table R301.2 (1) of the IRC Modify by inserting data in the table as follows:
Ground
Wind Design
Seism
Subject to Damage From
Winter
ka8arner,
Flood hazards
Aur
Meanic
Topographic affects,
Snow
Speed
Design
Frot
Design
Untlerlaymen
Freezing
g
Lead
Special wind region, or
0aceg°�'
Weathering
line
Termite
Temp
tg6yuired
NFIP
FIRM
Anodal
Maps
Index
Temp
mph)
depth
Wind-borne debris zone
25
115
No
A
Severe
42"
M� h,
-5-F
Yes
5/22M
2/16/07
2000
50-F
Ordinance No.
Page 6
Section R302.5.1 of the IRC. Delete Section R302.5.1 of the IRC and insert in lieu thereof the following:
R302.5.1 Opening protection. Openings from a private garage directly into a room used for sleeping purposes
shall not be permitted. Other openings between the garage and residence shall be equipped with solid wood
doors not less than 1 3/8 inches (35 mm) in thickness, solid or honeycombcore steel doors not less than 1 3/8
inches (35 mm) thick, or 20 -minute fire -rated doors.
Section R302.13 of the IRC. Delete Section R302.13 of the IRC entirely.
Section R304.1 of the IRC. Delete Section R304.1 of the IRC and insert in lieu thereof the following:
R304.1 Minimum area. Habitable rooms shall have a floor area of not less than 70 square feet .
Exception: Kitchens.
Section R310.6 of the IRC. Delete Section R310.6 in the IRC and insert in lieu thereof the following:
R310.6 Alterations or repairs of basements in structures built after May 10, 1989. An emergency escape and
rescue opening is not required where existing basements undergo alterations or repairs.
Alterations or repairs in structures built prior to May 10, 1989 shall conform to Appendix J Section AJ102.4
Replacement windows.
Exception: New sleeping rooms created in an existing basement shall be provided with emergency escape and
rescue openings in accordance with Section R310.1.
Section R312.2 of the IRC and 1015.8 of the IBC. Delete Section R312.2 of the IRC and 1015.8 of the IBC
entirely.
Section R313 of the IRC: Delete Section R313 of the IRC entirely.
Section R320.2 of the IRC. Add Section R320.2 in the IRC as follows:
R320.2 Accessibility for projects other than those mentioned in Section R320.1.
R 320.2.1 Scope. The provisions of this section are enacted to implement universal design features that provide
accessibility, usability and visit -ability for all.
R320.2.2 Definition. Public funds shall mean funding or assistance from the City of Iowa City or any agent
thereof through any of the following means:
1. a building contract or similar contractual agreement involving a City -funded program or fund;
2. any real estate received by the owner through a subsidy, lease, or donation by the City or its agents;
3. preferential tax treatment, bond assistance, mortgage assistance, or similar financial advantages
from the City or its agents;
4. disbursement of federal or state construction funds including a Community Development Block
Grant; or
5. a City contract to provide funding or a financial benefit for housing.
R320.2.3 Applicability. The amendment applies to new one- and two-family dwellings and is not required for
new townhouses, accessory apartments or existing structures for repairs, alterations, change of occupancy or
additions unless the square footage of the addition is more than 25% of the existing structure, then, the
addition must comply.
Exception: Applies to new townhouses constructed using public funds.
The minimum usability requirements are as follows:
1. Step -less Entrance: At least one building entrance must be designed, without encroaching into any
required parking space, that complies with the Iowa City Building Code standard for an accessible entrance on
an accessible route served by a ramp in accordance with section R311.8 or a no -step entrance. The accessible
route must extend from a vehicular drop-off, or parking to a building entrance. The entry door must have a
minimum net clear opening of thirty-two inches (32").
Exception:
1. If public funds are used the step -less entrance must be provided.
2. The building official may waive this requirement based upon the determination that strict compliance is
financially or environmentally impractical. Split-level and townhouse style homes may be exempted.
Note. Iowa City code only requires one parking space for single family dwellings.
2. Interior doors: At least one bedroom and one bathroom (if 3ither are provided) and
all other passage doorway headerwidths, on the level served by the designed step -less entrance,
must be framed to accommodate a minimum 38" clear rough opening. The framing for the doorway
width opening may be reduced to accommodate any door size
Exception:
1.If public funds are used the minimum door clear opening shall be thirty-two inches (32") when the door
is open ninety degrees (90 ), measured between the face of the door and the opposite stop.
2.Doors serving closets twenty-four inches (24") or less in depth need not be framed to 38" clear opening
width.
Note: A 34" door hung in the standard manner provides an acceptable 32" opening.
3. Sanitation facilities: There must be at least one bathroom containing a water closet (toilet) and
lavatory (sink) on the level of the dwelling to be accessed by the designed step -less entrance. The room
Ordinance No.
PageMll have a minimum thirty inches (30") by forty-eight inches (48") clear floor space at the water closet
and lavatory. The clear floor space can be shared by both fixtures. The clear floor space shall not be
obstructed by a doorway swing.
The plans must shvv a shower, bathtub or combination tub/shower can be provided within the room or an
adjoining room without removing part of the concrete floor to provide necessary plumbing to the future plumbing
fixture(s).
Exception:
1.If public funds are used a shower, bathtub or combination tub/shower shall be provided within the room.
2.Doors may swing into the clear floor space provided at any fixture if sufficient maneuvering space is
provided within the room for a person using a wheelchair or other mobility aid to enter and close the door,
use the fixtures, reopen the door and exit. Maneuvering space may include any knee space or toe space
available below bathroom fixtures.
37he building official may waive this requirement based on the determination that strict compliance is
financially impractical.
4.-W all Reinforcement: A bathroom must be provided with wood blocking installed within wall framing to
support grab bars as needed. The wood blocking, when measured to the center, will be located between
thirty-three inches (33") and thirty-six inches (36") above the finished floor. The wood blocking must be
located in all walls adjacent to and behind a toilet.
Exception: Backing is not required behind pre -manufactured showers and bathtubs.
5. Decks: All exterior decks and patios surfaces adjacent to the level served by the designed step -less
entrance must be built within four inches (4") of the dwellings finish floor level. Decks shall be a minimum 50%
the size of a patio that is served by level served by the designed step -less entranca.
6. Switch and outlet requirements: All wall switches, controlling light fixtures, fans, all
temperature control devices and all receptacles shall be located in an area between fifteen (15) and forty-
eight (48) inches above finished floor. The height will be determined by measuring from the finished
floor to the center of the device. When the control or receptacle placement is prohibited by the height of the
window or design feature, alternative locations may be approved by the building official.
7 Electrical panel requirements: Electrical panels on the level of the dwelling to be accessed by the
designed step -less entrance shall be located so that the individual circuit breakers are located between 15'
and 54 " above the floor.
8. Garages: Must be wired for power operated overhead
Section R322 of the IRC. Delete section R322 of the IRC and insert in lieu thereof the following:
R322. See Title 14 Chapter 5J Flood Plain Management Standards in the City Code.
R322.1 Flood Resistive Materials. Building materials and installation methods used for flooring and interior and
exterior walls and wall coverings below the elevation required in Title 14 Chapter 5,11 Flood Plain Management
Standards in the City Code shall be flood damage -resistant materials that conform to the provisions of FEMA
TB -2.
Section R326 of the IRC. Delete Section R326 of the IRC entirely.
Section R403.1.4.1 of the IRC. Modify by deleting all exceptions and inserting in lieu thereof the following:
Exceptions:
1. One story detached accessory buildings of wood or steel frame construction not used for human
occupancy and not exceeding one thousand (1,000) square feet in floor area may be constructed using
slab on grade construction as follows. The slab shall be three and one half inches thick, poured
monolithically with thickened perimeter footings extending twelve inches (12") below finish grade and be
sixteen inches (12") wide at the base. The top of the foundation shall not be less than six inches (6")
above finish grade. Reinforcement of the slab, including the thickened portion, shall be minimum
6x6-10/10 welded wire mesh, #4 deformed reinforcing bars at twenty four inches (24") on center each
way or fiber mesh reinforced concrete.
2. One-story wood or metal frame building not used for human occupancy and not over 200 square feet in
floor area may be constructed with walls supported on a wood foundation plate or "skids" when approved
by the building official.
3. Decks not supported by the structure need not be provided with footings that extend below the frost line.
Ordinance No.
Page 8
Section R404 1 1 of the IRC: Amend Section R404 1.1 of the IRC by adding an Exception after number 2 as follows
Exception: Foundation walls with unbalanced lateral forces created by finish grade, i.e. walkout basements
which are exempt from the Iowa Architectural Act shall be designed by a licensed structural engineer or
constructed in accordance with the Table R404.1.1(5) and diagram as follows:
CB a Comp Be,,
S m span of wall
T•Thlokness
o=4'Offset
CB
Table R401.1.1(5)
a" & 12" Foundation Walk
Prmide Former bars to match horbomal
Foundation wall minforokg Into well2'
Span Wall Thlconess IlorloomOmer Be,
5 (T) Belnforaln (CB
101 or less
e"
44 as II"
2'-V
IP to 12'
8"
a5@12"
2'-C
12'to 14'
8'.
96 @ 12"
3'-0"
14'to 16
12"
45 @ 12"
2' 6"
16'1018'
12"
Y6 @ 14"
3'-0"
n' to 20'
12"
#6 so 12"
3'-0"
Frost Wall &Footing (Walko t)
Notes:
1. Omer Bars are required In addition to horizontal reinforcing.
2. All Omer Bar reinforcing splices shall be lapped a minimum of 24".
B. If span (S) is greater than 15, the minimum dimension of (p shall be V.
Y.
Yl ..Y..
Inside Face of
Sae Schedule for
fldRmltal RBIIdoban
44 Reinforcing Viokal
30' O.C. Typical
/4 Reinforcing Dow
Section R404.1.3 of the IRC. Modify Section R404.1.3 by adding a second paragraph as follow s1
Wall thickness may be reduced to eight inches (B") if a minimum of three (3) one-half inch diameter
deformed ASTM A615 grade 40 steel bars are placed horizontally at the center of the wall thickness with
one bar located within 14" of the top, one bar within 14of the bottom and one bar located within 14" of
the mid -height of the wall provided the wall height does not exceed eight feet (8').
Section 423.4 of the IBC. Delete Section 423.4 in its entirety and insert in lieu thereof the following:
Group E occupancies. In areas where the shelter design wind speed for tornados is 250 MPH in
accordance with Figure 304.2(1) of ICC 500, all new Group E occupancies shall have a storm shelter
constructed in accordance with ICC 500. The shelter shall be capable of housing the total occupant load of
the Group E occupancy or as required by 661-301 of the Iowa State Building Code, whichever is more
restrictive.
Exceptions:
1, Group E day care facilities.
2. Group E occupancies accessory to places of religious worship.
3. Buildings meeting the requirements for shelter design in ICC 500.
4. Portable buildings.
Ordinance No.
Page 9
Section 501.2 of the IBC (F). Modify by inserting the following after the second sentence:
From 100-199 feet from the street the number shall be a minimum of 6 inches high with a minimum
stroke of 0.5 inches. From 200-299 feet from the street the numbers shall be a minimum 8 inches high
with a minimum stroke of 0.5 inches. For each additional 100 feet from the street, the number shall
increase by an additional 2 inches in height. Measurements to determine the minimum number size shall
be measured from the approved address location to the center line of the street for which the premises is
addressed.
Section R703.2 of the IRC. Modify by deleting the last sentence in the paragraph.
Section R807.1 of the IRC. Modify by adding a sentence at the end of the second paragraph as follows:
The opening shall not be located in a closet, bathroom, mechanical room, laundry room, or similar room or
location.
Ordinance No.
Page 10
Section 903.2.1.2 of the IBC (F). Modify section 903.2.1.2 by adding a second paragraph as follows:
Group A-2 Occupancies that existed prior to August 1, 2007:
An automatic sprinkler system shall be provided throughout the A-2 occupancy with an occupancy
load of 100 or more that have an ABDL and there is a change in business ownership, defined
as the sale, transfer, or assignment of any legal or equitable ownership interest, except that
the owner may show to the building official's satisfaction that said change in ownership is
one of form and not substance.
Section 903.2.1.8 of the IBC (F). Add a new Section 903.2.1.8 as follows:
Section 903.2.1.8. An automatic sprinkler system shall be provided throughout buildings and portions
thereof used as new Group B occupancies with an ABDL or existing group B occupancy with a new
(not a renewal) ABDL located on a floor other than the level of exit discharge. The automatic sprinkler
system shall be provided throughout the floor area where the new Group B occupancy with an ABDL
or where the group B occupancy with a new ABDL is located, and in all floors between the Group B
occupancy and the level of exit discharge.
Section 903.2.2 of the IBC (F). Delete Section 903.2.2 of the IBC and replace with:
903.2.2 Group B ambulatory health care facilities. An automatic sprinkler system shall be installed
throughout all fire areas containing a Group B ambulatory health care facility occupancy.
Section 903.3.5.3 of the IBC (F). Add a new Section 903.3.5.3 in the IBC to read as follows:
903.3.5.3 Water supply safety margin. Provide a minimum 10%, but not less than 5 psi, safety margin
above static pressure in the fire protection system hydraulic calculation.
Section 903.4.2 of the IBC (F). Delete Section 903.4.2 of the IBC and replace with:
903.4.2. Alarms. An approved weatherproof horn/strobe device shall be mounted directly above the
fire department connection between seven (7) and ten (10) feet in height above grade. The water -
flow alarm device shall be activated by water flow equivalent to the flow of a single sprinkler of the
smallest orifice size installed in the system. Approved and supervised audible visual notification
appliances shall be installed on each level of the interior of the building as required by the fire code
official and NFPA 72.
Section 903.6 of the IBC (F). Add a new Section 903.6 to the IBC to read as follows:
903.6 Zones. Automatic sprinkler system zones shall not exceed the area permitted by NFPA 13 or
NFPA 13R and shall provide a sprinkler control valve and water flow device for each normally occupied floor
Section 906.1 of the IBC (F). Delete the exception without substitution.
Section 906.3 of the IBC (F). Add a sentence to the end of the section to read as follows:
The minimum rating of any required portable fire extinguisher for Class A, Class B, or Class C
hazard shall be 2-10 B C
Section 907.2 of the IBC (F). Delete the section and replace with:
907.2 Where required -new buildings and structures. An approved and addressable fire alarm system
installed in accordance with the provisions of this code and NFPA 72 shall be provided in new
buildings and structures in accordance with Sections 907.2.1 through 907.2.23 and provide occupant
notification in accordance with 907.5, unless other requirements are provided by another section of this
code.
A minimum of one manual fire alarm box shall be provided in an approved location to initiate a fire
alarm signal for fire alarm systems employing automatic fire detectors or water -flow detection devices.
Where other sections of this code allow elimination of fire alarm boxes due to sprinklers, a single fire
alarm box shall be installed.
EXCEPTION:
1. The manual fire alarm box is not required for fire alarm systems dedicated to elevator recall
control and supervisory service.
Section 907.2.1 of the IBC (F). Delete the "exception" in Section 907.2.1 in its entirety and insert in lieu
thereof the following exceptions:
EXCEPTION:
1) Except for Group A-2 occupancies with occupant loads of 200 or more, manual fire alarm boxes
are not required where the building is equipped throughout with an automatic sprinkler system and the
alarm notification appliances will activate upon sprinkler water flow.
Ordinance No.
Page 11
2) Group A-2. An automatic/manual fire alarm system shall be installed in Group A-2 occupancies
with and occupant load of 200 or more. Activation of the Fre alarm shall
additionally cause:
a. Illumination of the protected premises to not less than 10 foot-candles over the area of the
room at a height of 30 inches above the floor; and
b. All conflicting or confusing sounds and visual distraction to automatically stop.
Section 907.2.3 of the IBC (F). Modify by adding a sentence to the end of the first paragraph as follows:
New and existing educational occupancies shall have a monitored fire alarm system.
Section 907.2.3 of the IBC (F). Modify by adding a 4 exception as follows:
4. Day care occupancies classified as Group E Occupancy shall not require a monitored fire alarm
system unless required elsewhere in the code.
Section 907.2.11.2 of the IBC. Modify by adding a fourth location requirement as follows:
4. Supervised smoke alarms shall be installed in all common corridors and at the top and bottom of all
stairway enclosures in Groups R-2, R-4 and 1-1 occupancies. In corridors, detectors shall be
located within fifteen (15) feet of the end of the corridor and in such a way that one detector is located for
each thirty (30) feet of corridor length or spaced as allowed by the code.
Section 907.4.2 of the IBC. Modify by adding a sentence to the end of the section to read as follows:
Where in the opinion of the code official manual fire alarm boxes may be used to cause false fire
alarms, the code official is authorized to modify the requirements for manual fire alarm boxes.
Section 907.6.4 of the IBC (F). Modify by deleting the exception and inserting in lieu thereof the following exception:
Exception: Automatic sprinkler system zones shall not exceed the area permitted by NFPA 13 and
shall provide a sprinkler control valve and waterflow device for each normally
occupied floor.
Section 907.6.4.3 of the IBC (F). Add a section to read as follows:
Section 907.6.4.3 Zone and address location labeling. Fire alarm and/or annunciator panels shall have all
zones and address points plainly and permanently labeled as to their location on the outside of the
panel or on an easily readable map of the building.
Section 907.6.6 of the IBC (F). Modify Section 907.6.6 by adding two sentences to the end as follows:
Each address point identification, shall have an alpha/numeric descriptor location. Alphanumeric
descriptor locations are required to be reported to the Emergency Communications Center upon
activation of supervisory and/or alarm conditions as specified by the fire code official.
Section 910.2 of the IBC (F). Delete exception 2 without substitution.
Section 910.3.2.2 of the IBC (F). Delete Section 910.3.2.2 and replace with:
910.3.2.2 Sprinklered buildings. Where installed in buildings provided with an approved automatic
sprinkler system, smoke and heat vents shall be designed to operate automatically by actuation
of a heat- responsive device rated at least 100 degrees F (38 degrees C) above the operating
temperature of the sprinkler.
Exception: Gravity -operated drop-out vents complying with Section 910.3.2.1
Section 910.4.3 of the IBC (F). Delete section 910.4.3 in its entirety and replace with:
910.4.3 Operation. Mechanical smoke exhaust fans shall be automatically activated by heat detectors
having operating characteristics equivalent to those described in Section 910.3.2. Individual manual
controls for each fan unit shall also be provided.
Section 912.6 of the IBC (F). Add a new section 912.6 to the IBC to read as follows:
912.6 Size. Minimum fire department connection size shall be 212 inch National Standard Thread.
Section 912.7 of the IBC (F). Add a new section 912.7 to the IBC to read as follows:
912.7 Water supply. Fire department connections shall be located not more than 100 feet from a
hydrant and both the fire department connection and hydrant shall be located on the same side of
the fire department access or as approved by the fire code official.
Section 1011.3 of the IBC. Modify by adding a third exception as follows:
Ordinance No.
Page 12
EXCEPTION:
3. Stairs within individual dwelling units of Residential Group R occupancies that existed prior to
8/28/02 (adoption of the 2000 IRC) are permitted a 78 -inch (6'-6") headroom clearance.
Section 1015.8 of the IBC. Delete Section 1015.8 of the IBC entirely.
Section 1023.4 of the IBC. Modify Section 1023.4 by adding a fourth unnumbered paragraph as follows:
Fire door assemblies that provide access to a non -pressurized interior exit of R-2 occupancies shall also be
automatic closing by actuation of a smoke detector.
Section 1029.2 of the IBC (F). Modify by adding two new exceptions as follows: EXCEPTION:
1) Except for Group A-2, in assembly occupancies where there is no well-defined main exit or
where multiple main exits are provided, exits shall be permitted to be distributed around the
perimeter of the building provided that the total width of egress is not less than 100 percent of the
required width.
2) The main entrance/exit of A-2 occupancies shall be of a width that accommodates not less than
two-thirds of the total occupant load.
Section 1030.1 of the IBC. Modify by deleting the exceptions and inserting in lieu thereof the following:
EXCEPTIONS:
1. The emergency escape and rescue opening is permitted to open onto a balcony within an atrium
in accordance with the requirements of Section 404 provided the balcony provides access to an
exit and the dwelling unit or sleeping room has a means of egress that is not open to the atrium.
2. Regardless of what Tables 1006.3.2(1) and 1006.3.2(2) allow, all group R-2 occupancies other than
hotels and motels must be provided with emergency escape & rescue openings.
3. Emergency escape and rescue openings are not required from basements or sleeping rooms
that have an exit door or exit access door that opens directly into a public way or to a yard, court or
exterior exit balcony that opens to a public way.
Section 1030.3 of the IBC. Modify by adding an exception as follows:
EXCEPTION: For emergency escape and rescue openings required for the remodeling or finishing of
space in an existing basement, the maximum sill height may be measured from an elevated
landing not less than 36 inches wide, not less than 18 inches out from the interior finish of the exterior
wall and not more than 24 inches in height. The landing shall be permanently affixed to the floor
below and the wall under the window it serves.
Section 1030.6 of the IBC. Add a new Section 1030.6 to the IBC to read as follows:
Section 1030.6. Emergency escape windows under decks and porches. Emergency escape windows
are allowed to be installed under decks and porches provided the location of the deck allows the
emergency escape window to be fully opened and provides a path not less than 36 inches in height to a
yard or court.
Chapter 11 of the IRC. Delete Chapter 11 in its entirety and insert in lieu thereof the following:
Chapter 11 Energy Efficiency, Section N1101. Energy efficiency for the design and construction of
building regulated by this code shall be as required by 661-303 of the Iowa State Administrative Code.
Chapter 11 of the IBC. Delete Chapter 11 in its entirety and insert in lieu thereof the following:
Chapter 11 Accessibility, Section 1101. Buildings or portions of buildings shall be accessible to persons
with disabilities as required by 661-302 of the Iowa State Administrative Code.
Section 1209.2 of the IBC. Modify by adding a second unnumbered paragraph as follows:
1209.2 Attic spaces. The opening shall be located in a corridor, hallway, or other readily accessible location.
The opening shall not be located in a closet, bathroom, mechanical room, laundry room, or similar room or
location. Attics with a maximum vertical height of less than thirty inches need not be provided with access
openings.
Chapter 13 of the IBC. Delete Chapter 13 in its entirety and insert in lieu thereof the following:
Chapter 13 Energy Efficiency, Section 1301. Energy efficiency for the design and construction of
building regulated by this code shall be as required by 661-303 of the Iowa State Administrative Code.
Section 1403.6 and 1403.7 of the IBC. Delete Sections 1403.6 and 1403.7 of the IBC and insert in lieu
thereof the following:
Section 1403.6. See Title 14, Chapter 5, Article J Flood Plain Management Standards in the City Code.
Ordinance No.
Page 13
Section 1612 of the IBC. Delete Section 1612 of the IBC and insert in lieu thereof the following:
Section 1612. See Title 14, Chapter 5 Article J Flood Plain Management Standards in the City Code.
Section G2406.2 (303.3) of the IRC. Prohibited locations of the IRC. Modify by deleting exceptions 3 and 4.
Section G2415.3 (404.3) of the IRC. Prohibited locations of the IRC.. Modify by deleting the last sentence.
Part VII Plumbing Chapters 25 through 33 inclusive of the IRC. Delete Part VII Plumbing Chapters 25
through 33 inclusive of the IRC and insert the following:
Part VII Plumbing, Chapter 25
Section P2501 GENERAL
P2501.1 Scope. Plumbing systems shall comply with the Iowa State Plumbing Code.
Administrative Provisions. The Plumbing Code shall be administered in accordance with administrative
provisions in chapter 1 of this code as amended.
Chapter 27 of the IBC. Delete Chapter 27 of the IBC and insert the following:
Chapter 27 Electrical
Section 2701.1 Scope. Electrical systems shall comply with the Iowa State Electrical Code.
Administrative Provisions. The Electrical Code shall be administered in accordance with administrative
provisions in chapter 1 of this code as amended and Appendix K as amended.
Chapter 28 of the IBC. Delete chapter 28 of the IBC and insert the following:
Chapter 28 Mechanical Systems
Section 2801.1 Scope. Mechanical systems shall comply the Iowa State Mechanical Code with the following
amendments:.
Administrative Provisions. The Mechanical Code shall be administered in accordance with administrative
provisions in chapter 1 of this code as amended.
Commercial Kitchen Hood Exhaust Termination:
In addition to the code requirements for commercial kitchen hood exhaust terminations locations, the following
shall apply:
For new construction, change in occupancy or change in use, that requires a new commercial kitchen hood or
revisions to an existing commercial kitchen hood, the new or existing commercial kitchen hood exhaust duct
shall terminate as follows:
1. Above the roof level without passing through an exterior wall; or
2. Through an alley facing exterior wall provided the termination is above the roof level; or
3. To an alley right of way per 3202.3.2 of the International Building Code.
Chapter 29 of the IBC. Delete Chapter 29 of the IBC and insert the following
Chapter 29 Plumbing Systems
Section 2901.1 Scope. Plumbing systems shall comply with the Iowa State Plumbing Code.
Administrative Provisions. The Plumbing Code shall be administered in accordance with administrative
provisions in chapter 1 of this code as amended.
Section 3002.4 of the IBC. Delete Section 3002.4 of the IBC and insert in lieu thereof the following:
3002.4 Elevator car to accommodate ambulance stretcher.
In buildings four or more stories above, or four or more stories below, grade plane, at least one
elevator shall be provided for fire department emergency access to all floors. The elevator car shall be
of such a size and arrangement to accommodate an ambulance stretcher 24 inches by 84 inches (610
mm by 2134 mm) with not less than 5 -inch (127 mm) radius corners, in the horizontal, open position
and shall be identified by the international symbol for emergency medical services (star of life). The
symbol shall not be less than 3 inches (76 mm) high and shall be placed inside on both sides of the
hoistway door frame.
Ordinance No.
Paae 14
Delete Part VIII Electrical Chapters 34
through 43 inclusive of the IRC and insert the following:
Part VIII Electrical, Chapter 34
Section E3401 GENERAL
E3401.1 Applicability. Electrical systems shall comply with the Iowa State Electrical Code.
(Appendix K of the IBC.)
Section K103.2 of the IBC. Work exempt from permit. Delete Section K103.2 in the IBC and insert in lieu thereof the
following:
Section K103.2 Work exempt from permit. See section 105.2 in both the IRC and IBC.
Section K706.5 of the IBC. Add a new Section K106. 5 as follows:
Section K106. 5 Energy Connections; An electrical system or equipment regulated by this code for which
a permit is required shall not be connected to a source of energy or power until approved by the building
official.
Section K106.6 of the IBC. Add a new Section K106. 6 as follows:
Section K106. 6 Temporary Energy Connections. The building official may authorize the temporary
connection of the electrical system or equipment to the source of energy or power for the purpose of
testing the equipment, or for use under a temporary certificate of occupancy.
(Appendix J of the IRC. )
Section AJ102.4 of the IRC. Delete Section AJ102.4 of the IRC and insert in lieu thereof the following:
A.11 02.4 Replacement windows and doors. Regardless of the category of work, where an existing window or
door, including the sash and glazed portion, or safety glazing is replaced, the replacement window, door or
safety glazing shall comply with the requirements of Sections AJ102.4.1 through AJ102.4.3, as applicable.
Section AJ102.4.1 of the IRC. Delete Section AJ102.4.1 of the IRC and insert in lieu thereof the following:
AJ102.4.1 Energy efficiency. Replacement windows or doors shall comply with the requirements of Chapter 11.
Section AJ102.4.4 of the IRC. Delete Section AJ102.4.4 of the IRC entirely.
Section AJ501.7 of the IRC. Delete Section AJ501.7 and insert in lieu thereof the following:
AJ501.7 Ceiling height. Habitable spaces created in existing basements or attics shall have ceiling heights of
not less than 6 feet, 8 inches (2032 mm), except that the ceiling height at obstructions shall be not less than 6
feet 4 inches (1930 mm) from the basement or attic floor. Existing finished ceiling heights in nonhabitable
spaces in basements or attics shall not be reduced.
Section AJ501.8.1 of the IRC. Delete Section AJ501.8.1 of the IRC and insert in lieu thereof the following:
AJ501.8.1 Stair width. Existing basement and attic stairs and handrails not otherwise being altered or modified
shall be permitted to maintain their current clear width at, above and below existing handrails.
Section AJ501.8.2 of the IRC. Delete Section AJ501.8.2 of the IRC and insert in lieu thereof the following:
AJ501.8.2 Stair headroom. Headroom height on existing basement orattic stairs being altered or modified shall
not be reduced below the existing stairway or attic finished headroom. Existing basement or attic stairs not
otherwise being altered shall be permitted to maintain the current finished headroom.
Section AJ501.8.3 of the IRC. Delete Section AJ501.8.3 of the IRC and insert in lieu thereof the following:
AJ501.8.3 Stair landing. Landings serving existing basement or attic stairs being altered or modified shall not
be reduced below the existing stairway landing depth and width. Existing basement or attic stairs not otherwise
being altered shall be permitted to maintain the current landing depth and width.
Section AJ601.4 of the IRC. Delete Section AJ601.4 of the IRC and insert in lieu thereof the following:
AJ601.4 Ceiling height. Habitable spaces created in existing basements and attics shall have ceiling heights of
not less than 6 feet, 8 inches (2032 mm), except that the ceiling height at obstructions shall be not less than 6
feet 4 inches (1930 mm) from the basement or attic floor. Existing finished ceiling heights in nonhabitable
spaces in basements or attics shall not be reduced.
17-1-4: Penalties for violations: Violation of this chapter shall be a municipal infraction punishable by a
penalty as provided for in subsection 1-4-2D of the City Code.
SECTION III. EFFECTIVE DATE. This Ordinance shall be in effect after final passage, approval and publication as
provided by law.
Ordinance No.
Page 6
CITY OF IOWA CITY
MEMORANDUM
Date: May 14, 2015
To: Board of Appeals
From: Brian Greer, Fire Marshal
Re: Notable changes to the 2015 edition of the International Fire Code
The fire department presents for your review, notable changes to the 2015 International Fire Code (IFC).
105.4.5 NEW SECTION. Amended Construction Documents- The 2015 code now requires
submittal of amended construction documents if changes were made during construction.
107.3 NEW SECTION. Recordkeeping — Records shall be kept for not less than three years
for inspections, tests, service, and maintenance of equipment or systems. The fire code
official can prescribe the form and format of these records..
202 NEW DEFINITIONS. General Definitions —New definitions for egress system
components, new technology and other general definitions.
308.1.6.2 NEW SECTION. Sky Lanterns — Prohibits the release of an untethered sky lantern.
403 NEW SECTION. Emergency Preparedness Requirements — The requirements in this
section discuss fire safety plans, seating plans, evacuation drills, and staff training
necessary in a multitude of occupancy classifications.
503 REVISED SECTION. Fire Apparatus Roads — Provides more exceptions and latitude
for the fire code official.
510.4.2.3 NEW SECTION. Standby Power — Establishes requirements for standby power for
emergency responder radio coverage systems.
604 NEW SECTION. Emergency and Standby Power Systems — Large section detailing
emergency power system requirements for the system itself and different devices,
occupancies, and communication equipment. From IBC for uniformity.
610 NEW SECTION. Commercial Kitchen Cooking Oil Storage — New section on storage
tanks and their design and venting in regards to cooking oil.
807 REVISED SECTION. Decorative Materials... in New and Existing Buildings — New
requirements and limitations for furnishings in A, E, I, and R occupancies.
903.2.1.6 NEW SECTION. Assembly Occupancies on Roofs — Establishes requirements for
automatic sprinklers for an A-2 occupancy with an occupant load of 100 and 300 for
other A occupancies and sprinkler on floors between roof and exit discharge.
907.2.11.3 NEW SECTION. Installation Near Cooking Appliances — Establishes requirements for
where ionization and photoelectric smoke alarms shall be installed near a cooking
appliance.
910 NEW SECTION. Smoke and Heat Removal — Establishes design and operations of
smoke and heat vents as well as mechanical smoke removal systems clearing up previous
issues with design and operations.
915 NEW SECTION. Carbon Monoxide Detection — Establishes new requirements for
installation of carbon monoxide detection in new buildings and also the use of
combination detectors as an alternative.
Chap. 10 REVISED SECTION. Means of Egress — The whole chapter has been reformatted with
changes to the code text too extensive to reprint.
1103.4.1 MODIFIED SECTION. Vertical Openings -Group I-2 and I-3 occupancies —
Retroactive construction of a 1 -hour fire -resistance -rated separation in existing hospitals
and jails to protect vertical openings.
1103.7.6 REVISED SECTION. GroupR-2 Exceptions — Added an exception for hard -wired,
interconnected smoke alarms to replace the need for manual fire alarm system in certain
occupancies..
2307.4 MODIFIED SECTION. LP -gas Dispensing Operations — LP -gas requirements revised
to improve correlation with other industry standards and allow public refueling self-
service.
2808 MODIFIED SECTION. Storage and Processing of wood chips,.... and recycling
facilities — Added additional exceptions for pile size related to sound fire prevention and
protection principles.
3103.9.1 MODIFIED SECTION. Structural Design of Multistory Tents and Membrane
Structures — Temporary multistory tents and membrane structures must comply with
structural requirements in the IBC.
3105 NEW SECTION. Temporary Stage Canopies — Temporary stage canopies are now
permitted and regulated under Chapter 31.
3304 MODIFIED SECTION. Fire Safety During Construction and Demolition — Provided
more direction for precautions against fire for combustible debris, waste, and rubbish.
3206.9.3 CLARIFICATION. Dead-end Aisles in High piles Combustible Storage — Provides
specific limitations for these aisles.
3510 NEW SECTION. Hot Work on Flammable and Combustible Liquid Storage Tanks —
Provides requirements for hot work on tanks containing flammable and combustible
liquids.
5003.1.1(1) MODIFIED SECTION. Maximum Allowable Quantities of Hazardous Materials—
This table contains revisions affecting consumer fireworks, combustible fibers, alcohol -
based hand rubs, and other hazardous materials.
5307 NEW SECTION. Carbon Dioxide Systems Used in Beverage Dispensing Applications
— Regulation of these systems now included in the 2015 IFC.
5808 NEW SECTION. Hydrogen Fuel Gas Rooms — Requirements applicable to hydrogen
fuel gas rooms has been included in the IFC.
Prepared by: Brian Greer, Fire Marshal, 410 E. Washington Street, Iowa City, IA 52240
ORDINANCE NO. 15 —XXXX
AN ORDINANCE AMENDING TITLE 7, CHAPTER 1, FIRE CODE, BY ADOPTING THE 2015 EDITION
OF THE INTERNATIONAL FIRE CODE TO REGULATE AND GOVERN THE SAFEGUARDING OF
LIFE AND PROPERTY FROM FIRE AND EXPLOSION HAZARDS ARISING FROM THE STORAGE,
HANDLING AND USE OF HAZARDOUS SUBSTANCES, MATERIALS AND DEVICES, AND FROM
CONDITIONS HAZARDOUS TO LIFE OR PROPERTY IN THE OCCUPANCY OF BUILDINGS AND
PREMISES IN THE CITY OF IOWA CITY AND PROVIDING FOR THE ISSUANCE OF PERMITS.
NOW, THEREFORE, BE IT ORDAINED BY THE CITY COUNCIL OF THE CITY OF IOWA CITY,
IOWA:
SECTION I. AMENDMENT.
1. Section 1, entitled, "Fire Code Adopted," is hereby deleted and the following new Section 1 is
inserted in lieu thereof:
That a certain document, one (1) copy of which is on file in the office of the City Clerk of the City of
Iowa City, being marked and designated as the International Fire Code, 2015 edition, including errata and
Appendix Chapters B, C, D, E, F, G, H. I, J, and K as published by the International Code Council, be and
is hereby adopted as the Fire Code of the City of Iowa City, in the State of Iowa regulating and governing
the safeguarding of life and property from fire and explosion hazards arising from the storage, handling
and use of hazardous substances, materials and devices, and from conditions hazardous to life or
property in the occupancy of buildings and premises as herein provided, providing for the issuance of
permits and each, and all of the regulations, provisions, penalties, conditions and terms of said Fire Code
on file in the office of the City Clerk are hereby referred to, adopted and made a part hereof, as if fully set
out in this ordinance, with the additions, Insertions, deletions and changes, prescribed in the following
sections of this ordinance.
2. Section 2, entitled "Amendments to Fire Code," Is deleted in Its entirety and the following new
Section 2 is inserted in lieu thereof.
That the following sections are hereby revised:
Section 101.1 Insert: Iowa City, Iowa
Section 102.1 Modify by adding a fifth applicability requirement to the end as follows:
5. A. All A-2 Occupancies that existed prior to August 1, 2007 with an occupant load of 100-298 with
an ABDL shall comply with Section 903.2.1.2, provided that there is a change in business ownership,
defined as the sale, transfer, or assignment of any legal or equitable ownership interest, except that the
owner may show to the building official's satisfaction that said change in ownership is one of form and not
substance.
EXCEPTION Single business occupancies in single story non -abutting buildings.
Section 104.1.1 Add a new section to read as follows: The code official and members of the fire
prevention bureau shall have the powers of a peace officer in performing their duties under this Code.
Section 104.1.2 Add a new section to read as follows: The Fire Chief may appoint and designate
such members of the Fire Department as fire/police investigators upon being certified by the Iowa Law
Enforcement Academy. Fire/police investigators shall have the powers of a peace officer in performing
their duties under this Code, including full powers of arrest to effectuate their duties of enforcing city
ordinances and state statutes. Notwithstanding his/her status as a peace officer, a fire/police investigator
shall be subject to the rules and regulations of the Iowa City Fire Department for all purposes and shall
perform such functions as the Fire Chief shall assign.
Section 104.12 Add a new section to read as follows: The code official is authorized to order an
operation or use stopped, or the evacuation of any premises, building, or vehicle or portion thereof which
has or is a fire, life safety or health hazard.
Ordinance No.
Page 2
Section 105.2 Add a sentence to the end of the section to read as follows: Application for an
operational permit shall be submitted with all required information not less than 14 days prior to the event
requiring a permit.
Section 106.2 Add a sentence to the end of the section to read as follows: The fire code official at the
official's sole discretion may send plans to a qualified agency for review. The fire code official shall
designate the plans review agency. The applicant shall pay all fees associated with the plan review
directly to the outside agency.
Section 108. Delete in its entirety and insert in lieu thereof: See Title 17 Chapter 12 of this Code.
Section 109.4 Delete the section and replace with: Persons who shall violate a provision of this code
or shall fail to comply with any of the requirements thereof or who shall erect, install, alter, repair or do
work in violation of the approved construction documents or directive of the fire code official, or of a
permit or certificate used under provisions of this code, shall be guilty of a simple misdemeanor or
municipal infraction, as prescribed in 1-4-2D. Each day that a violation continues after due notice has
been served shall be deemed a separate offense.
Section 111.4 Delete the section and replace with: No person shall continue any work after having
been served with a stop work order, except such work as that person is directed to perform to remove a
violation or unsafe condition
Section 202 Add a new definition to read as follows: CODE OFFICIAL. The Chief Officer of the Fire
Department, the Fire Marshal, or the Chiefs authorized representative.
Section 202 Add a new definition to read as follows: CROWD MANAGEMENT. Crowd management
meshes the design features of a facility, the established operating features of that facility, and an
understanding of the occupants' expected natural behavior in that facility for a specific type of event.
Section 202 Add a new definition to read as follows: EMERGENCY COMMUNICATIONS CENTER.
The Johnson County Joint Emergency Communications Center.
Section 202 Add a sentence to the end of FIRE LANE definition to read as follows: See City Code 9-
4-13 for additional rules and regulations.
Section 202 Delete the existing R-4 definition and substitute the following: R-4 Residential
occupancies shall include buildings arranged for occupancy as residential care/assisted living facilities
including more than five but not more than 16 occupants, excluding staff.
Group R-4 occupancies shall meet the requirements for construction as defined in the
International Building Code for Group R-3, except as otherwise provided for in that code.
Section 307 See also 6-6 of this Code.
Section 307.1.1 Delete the section and replace with: Prohibited burning. Burning that is offensive or
objectionable because of smoke or odor emissions or when atmospheric conditions or local
circumstances make such fires hazardous shall be prohibited.
Section 307.1.2 Add a new section to read as follows: Hours of operation. A person shall not
maintain any outdoor burning from 11 p.m. to 7 a.m. unless permitted and approved by the fire code
official.
Ordinance No,
Page 3
Section 307.3 Delete the section and replace with: Extinguishment authority. The fire code official is
authorized to order the extinguishment by the responsible person or the fire department of any burning
that creates or adds to a hazardous or objectionable situation.
Section 315.3 Add a sentence to the end of the section to read as follows: Combustible material
storage shall be confined to approved storage areas, such that the presence of incidental storage in any
other area of the building does not constitute a hazard.
Section 401.9 Add a new section to read as follows: Building evacuation. Upon activation of the
building fire alarm system or upon notification by other means of detecting and reporting unwanted fire, all
building occupants shall promptly evacuate the building.
EXCEPTION: When the emergency evacuation plan, as approved by the fire code official, does
not require the immediate total evacuation of the building.
Section 402.1 Add a new definition to read as follows: CROWD MANAGEMENT. Crowd
management meshes the design features of a facility, the established operating features of that facility,
and an understanding of the occupants' expected natural behavior in that facility for a specific type of
event.
Section 403.4 Add a new section to read as follows: A-2 Occupancy Crowd Managers. Group A-2
occupancies shall be provided with a minimum of one (1) trained crowd manager anytime occupancy
reaches 50 or more. Where the occupant load exceeds 250, additional trained crowd managers shall be
provided at a ratio of one (1) crowd manager for every 250 occupants. The crowd manager shall annually
receive training approved by the fire code official in crowd management techniques.
Section 405.2 Add to the end of the section as follows: Fire and evacuation drills in Group E
occupancies shall be conducted in accordance with Section 100.31 of the Code of Iowa. Fire drills in
Group R. Division 2, Fraternities and Sororities, shall be conducted once per academic semester.
Section 503.2.9 Add a new section to read as follows: Thickness. Fire apparatus access roads shall
be constructed of Portland cement concrete conforming to the specifications of the Iowa Department of
Transportation C-3 or M-3 mixes. The concrete access road shall be a minimum of 7 inches thick over
compacted soil.
Section 505.1 Delete the section and replace with: New and existing buildings shall have approved
address numbers, building numbers or approved building identification placed in a position that is plainly
legible and visible from the street or road fronting the property. Address identification characters shall
contrast with their background. Address numbers shall be Arabic numbers or alphabetical letters.
Numbers shall be a minimum of 4 inches high with a minimum stroke width of 0.5 inch. From 100-199 ft
from the street the number shall be a minimum of 6 inches high with a minimum stroke of 0.5 inches.
From 200-299 ft from the street the number shall be a minimum of 8 inches high with a minimum stroke of
0.5 inches. For each additional 100 ft from the street, the number shall increase by an additional 2 inches
in height. Measurements to determine the minimum number size shall be measured from the approved
address location to the center line of the street for which the premises is addressed. Where access is by
means of a private road and the building cannot be viewed from the public way, a monument, pole or
other sign or means shall be used to identify the structure. Address identification shall be maintained.
Section 506.1 Add a sentence to the end of the section to read as follows: An approved key box shall
be installed in an approved location on all new construction.
EXCEPTION: Group R-3 and unsecured R-2 occupancies.
Section 507.5.1 Delete exceptions 1 & 2.
Section 507.5.1.1 Delete the section and replace with: Hydrant for fire sprinkler and standpipe
systems. A fire hydrant shall be located not more than 100 feet from a fire sprinkler or standpipe system
Ordinance No.
Page 4
connection and on the same side of the fire department access as the connection or as approved by the
code official.
Section 510.1 Delete exception 1
Section 605.9 Delete the section and replace with: Temporary wiring. Temporary wiring for electrical
power and lighting installations is allowed for a period not to exceed 90 days for holiday decorative
lighting, carnivals and similar purposes. Temporary wiring methods shall meet the applicable provisions of
the Iowa City Electrical Code.
EXCEPTION: Temporary wiring for electrical power and lighting installations is allowed during periods
of construction, remodeling, repair or demolition of buildings, structures, equipment or similar activities.
Temporary wiring methods shall meet the applicable provisions of the Iowa City Electrical Code.
Section 605.10.5 Add a new section to read as follows: Fully enclosed. Portable, electric space
heaters shall be fully enclosed space heaters that by design have no external surfaces that reach
temperatures capable of igniting materials placed against the surface.
Section 804.5 Add a new section to read as follows: Maintenance. The interior finish of buildings
shall be maintained in accordance with the conditions of original approval. Any change to the interior
finish that is regulated by the provisions of this code or the building code shall be made in accordance
with all applicable requirements.
Section 806.1 Add a sentence to the end of the section to read as follows: Natural or resin -bearing
cut trees and natural decorative vegetation used in buildings open to the general public shall be properly
treated with an approved flame retardant.
Section 806.1.1 Delete the section and replace with: Restricted occupancies. Natural cut trees shall
be prohibited in Group A, B, E, 1-1, 1-2, 1-3, 1-4, M. R-1, and R-4 occupancies.
EXCEPTION: Trees located in areas protected by an approved automatic sprinkler system installed in
accordance with Section 903.3.1.1 or 903.3.1.2 shall not be prohibited in Groups A, B, E, M and R-1.
Section 807.5.2.1 Delete exceptions 1 & 2.
Section 807.5.5.1 Delete exceptions 1 & 2.
Section 901.2 (a) Add a new section to read as follows: Water based fire protection systems. Working
plans submitted to the fire department for water based fire protection systems shall be stamped and
approved by a qualified person to be in compliance with applicable NFPA standards and the Iowa City
Fire Code. Any changes to the working plans shall be approved by a qualified person. A qualified person
shall have a minimum National Institute for Certification in Engineering Technologies [NICET] Level III
certification for Automatic Sprinkler System Layout OR be a licensed engineer with experience in life
safety system design. Other qualifications may be approved by the code official.
Section 901.2 (b) Add a new section to read as follows: Fire alarm systems. Working plans submitted
to the fire department by a qualified person for fire alarm systems shall be stamped and approved by a
qualified person to be in compliance with applicable NFPA standards and the Iowa City Fire Code. Any
changes to the working plans shall be approved by a qualified person. A qualified person shall have a
minimum National Institute for Certification in Engineering Technologies [NICET] Level III certification for
Fire Alarm Systems OR be a licensed engineer with experience in life safety system design. Other
qualifications may be approved by the code official.
Section 903.1.2 Add a new section to read as follows: Water supply safety margin. Automatic
sprinkler systems shall be designed with a minimum of 10% or 5 psi safety margin (whichever is greater)
above static pressure in the fire protection system hydraulic calculations.
Section 903.2.1.2 Delete Section 903.2.1.2 and insert in lieu thereof the following:
Ordinance No.
Page 5
Section 903.2.1.2
A. New Group A-2 Occupancies. An automatic sprinkler system shall be provided for fire areas
containing Group A-2 occupancies and intervening floors of the building where one of the following
conditions exist:
1) The fire area exceeds 5,000 square feet;
2) The fire area has an occupant load of 100 or more; or
3) The fire area is located on a floor other than the level of exit discharge.
B. Existing Group A-2 Occupancies that existed prior to August 1, 2007:
An automatic sprinkler system shall be provided throughout the A-2 occupancy with an occupant load of
100 or more that have an ABDL and there is a change in business ownership, defined as the sale,
transfer, or assignment of any legal or equitable ownership interest, except that the owner may show to
the building official's satisfaction that said change in ownership is one of form and not substance.
EXCEPTION: Single business occupancies in single story non -abutting buildings.
Section 903.2.1.8 Add a new Section to read as follows: An automatic sprinkler system shall be
provided throughout buildings and portions thereof used as new Group B occupancies with an ABDL or
existing group B occupancy with a new (not a renewal) ABDL located on a floor other than the level of exit
discharge. The automatic sprinkler system shall be provided throughout the floor area where the new
Group B occupancy with an ASDL or where the group B occupancy with a new ABDL is located and in all
floors between the Group B occupancy and the level of exit discharge.
Section 903.2.2 Delete the section and replace with: Ambulatory care facilities. An automatic sprinkler
system shall be installed throughout all fire areas containing an ambulatory care facility and all floors
between the ambulatory care facility and the level of exit discharge serving such a facility.
Section 903.4.2 Delete the section and replace with: Alarms. An approved weatherproof horn/strobe
device shall be mounted directly above the fire department connection between seven (7) and ten (10)
feet in height above grade. The water -flow alarm device shall be activated by water flow equivalent to the
flow of a single sprinkler of the smallest orifice size installed in the system. Approved and supervised
audible visual notification appliances shall be installed on each level of the interior of the building as
required by the fire code official and NFPA 72.
Section 903.7 Add a new section to read as follows: Zones. Automatic sprinkler system zones shall
not exceed the area permitted by NFPA 13 or NFPA 13R and shall provide a sprinkler control valve and
waterflow device for each normally occupied floor. The location of sprinkler control valves must be
approved by the fire code official.
Section 906.1 Delete the exception without substitution.
Section 906.3 Add a sentence to the end of the section to read as follows: The minimum rating of any
required portable fire extinguisher for Class A, Class B, or Class C hazard shall be 2-A, 10-B C.
Section 907.1.4 Add a new section to read as follows: Fire alarm control panels and Fire alarm
annunciator panels. Installation of fire alarm control panels and fire alarm annunciator panels shall be
installed in accordance with section 907.1.4.1 through 907.1.4.5.
Section 907.1.4.1 Add a new section to read as follows: Fire Alarm Panel Height: Installation of fire
alarm panels shall not exceed 6 feet in height measured from the floor to the top of the panel. Exception:
Panel height may be altered by the code official.
Section 907.1.4.2 Add a new section to read as follows: Number of Fire Alarm Control Panels in
Buildings: Only one listed fire alarm control panel shall be allowed per building and shall lock in the alarm
until the system is reset and shall not be canceled by the operation of an audible — alarm silencing switch.
This control panel shall only receive alarm signals from fire protection equipment.
Ordinance No.
Page 6
Section 907.1.4.3 Add a new section to read as follows: Combination Fire/Security Alarm System
Panels. A listed combination fire/security alarm system panel that meets all the requirements of this code
and amendments may be permitted by approval of the fire code official. The fire/security panel shall be
capable of providing a signal that can differentiate between the fire and security alarm.
Section 907.1.4.4 Add a new section to read as follows: Password/PIN Protection Prohibited: Fire
alarm control panels and/or fire alarm annunciator panels that require a password/PIN to silence an
alarm/supervisory/trouble signal and/or to reset an alarm/supervisory/trouble signal shall be prohibited.
Section 907.1.4.5 Add a new section to read as follows: Fire Alarm Annunciator Panels: The fire code
official can require the addition of fire alarm annunciator panels based on the size of building and access
to the building. These panels shall meet the requirements of Sections 907.1.4 and 907.2.
Section 907.2 Delete the section and replace with: Where required—new buildings and structures. An
approved and addressable fire alarm system installed in accordance with the provisions of this code and
NFPA 72 shall be provided in new buildings and structures in accordance with Sections 907.2.1 through
907.2.23 and provide occupant notification in accordance with 907.5, unless other requirements are
provided by another section of this code.
A minimum of one manual fire alarm box shall be provided in an approved location to initiate a fire
alarm signal for fire alarm systems employing automatic fire detectors or water -flow detection devices.
Where other sections of this code allow elimination of fire alarm boxes due to sprinklers, a single fire
alarm box shall be installed.
EXCEPTION:
1. The manual fire alarm box is not required for fire alarm systems dedicated to elevator recall control
and supervisory service.
Section 907.2.1 Delete the exception in Section 907.2.1 in its entirety and insert in lieu thereof the
following exceptions:
EXCEPTION:
1) Except for Group A-2 occupancies with occupant loads of 200 or more, manual fire alarm boxes
are not required where the building is equipped throughout with an automatic sprinkler system
and the alarm notification appliances will activate upon sprinkler water flow.
2) Group A-2. An automatic/manual fire alarm system shall be installed in Group A-2 occupancies
with occupant loads of 200 or more. Activation of the fire alarm shall additionally cause:
a. Illumination of the protected premises to not less than 10 foot-candles over the area of
the room at a height of 30 inches above the floor; and
b. All conflicting or confusing sounds and visual distraction to automatically stop.
Section 907.2.3 Modify by adding a sentence to the end of the first paragraph as follows:
New and existing educational occupancies shall have a monitored fire alarm system.
Section 907.2.3 Modify by adding a 51" exception as follows:
5. Day care occupancies classified as Group E Occupancy shall not require a monitored fire alarm system
unless required elsewhere in the code.
Section 907.2.9.1 Delete exception 2 without substitution.
Section 907.2.11.2 Modify by adding a fourth location requirement as follows:
4) Supervised smoke alarms shall be installed in all common corridors and at the top and bottom of all
stairway enclosures in Groups R-2, R-4 and 1-1 occupancies. In corridors, detectors shall be located
within fifteen (15) feet of the end of the corridor and in such a way that one detector is located for each
thirty (30) feet of corridor length or spaced as allowed by the code.
Section 907.2.13.2 Delete the section without substitution.
Ordinance No.
Page 7
Section 907.4.2 Add a sentence to the end of the section to read as follows: Where in the opinion of
the code official manual fire alarm boxes may be used to cause false fire alarms, the code official is
authorized to modify the requirements for manual fire alarm boxes.
Section 907.6.4 Modify by deleting the exception and inserting in lieu thereof: Exception: Automatic
sprinkler system zones shall not exceed the area permitted by NFPA 13 and shall provide a sprinkler
control valve and waterflow device for each normally occupied floor.
Section 907.6.4.3 Add a section to read as follows: Zone and address location labeling. Fire alarm
and/or annunciator panels shall have all zones and address points plainly and permanently labeled as to
their location on the outside of the panel or on an easily readable map of the building.
Section 907.6.6 Add to the end of the section as follows: Each address point identification shall have
an alpha/numeric descriptor location. Alpha/numeric descriptor locations are required to be reported to
the Emergency Communications Center upon activation of alarm conditions as specified by the fire code
official. Supervisory alarm conditions are required to be reported to the fire code official by an approved
manner.
Section 910.2 Delete exceptions 2 and 3 without substitution.
Section 912.8 Add a section to read as follows: Size. Minimum fire department connection size shall
be 2'/2" National Standard Thread.
Section 1029.2 Add the following exception:
EXCEPTION: The main entrance/exit of A-2 occupancies shall be of a width that accommodates not
less than two-thirds of the total occupant load.
Section 1030.1 Modify by deleting exceptions 1 and 3.
Section 3206.7 Modify by deleting footnote "J" from TABLE 3206.2.
Section 5003.5 Add a sentence to the end of the section to read as follows: Signs shall also comply
with the requirements of the Iowa Right to Know law.
Section 5601.1.3 Delete exception 4 and insert in lieu thereof: The possession, storage, sale,
handling and use of gold star producing sparklers on wires which contain no magnesium or chlorate or
perchlorate, flitter sparklers in paper tubes that do not exceed one-eighth of an inch in diameter, toy
snakes which contain no mercury or caps used in cap pistols.
Section 5704.2.9 Add a sentence to the end of the section to read as follows: For aboveground
storage tanks of 276 gallons capacity or more, the minimum distance between such aboveground tanks
and any Residential Zone boundary must be at least 100 feet. If the aboveground tank is located in an
approved vault, the minimum separation distance from a Residential Zone boundary may be reduced to
no less than 50 feet.
Section 5704.2.11.1 Add a #4 to the end of the section to read as follows:
4) A minimum distance of ten (10) feet shall be maintained between underground tanks and any
Residential Zone boundary.
Section 5704.2.13.2.4 Add a section to read as follows: Existing above -ground tank hazards.
Existing above -ground tank installations, even if previously approved, that are determined to constitute a
hazard by the fire code official, shall not be continued in service. Unsafe tanks shall be removed as
required by the fire code official and in accordance with this code.
Section 5705.5.1 Add an exception to read as follows:
6) Corridor installations are prohibited in Group -E occupancies.
Ordinance No.
Page 8
3. Section 3. That the geographic limits referred to in certain sections of the 2015 International Fire
Code are hereby established as follows:
Section 5704.2.9.6.1. The storage of Class I and Class If liquids in above -ground tanks outside of
buildings is prohibited in the entire City of Iowa City, Iowa.
Exception: Zones 1 1 &2, Cl 1 and/or as approved by the Fire Chief.
Section 5706.2.4.4. The storage of Class I and Class II liquids in above -ground tanks is prohibited in
the entire City of Iowa City, Iowa.
Exception: Zones 1 1&2, Cl 1 and/or as approved by the Fire Chief.
Section 6104.2. The storage of liquefied petroleum gas is prohibited in the entire City of Iowa City,
Iowa.
Exception: Zones 1 1&2, Cl 1 and/or as approved by the Fire Chief.
SECTION II. REPEALER. All ordinances and parts of ordinances in conflict with the provisions of this
Ordinance are hereby repealed.
SECTION 111. SEVERABILITY. If any section, provision or part of the Ordinance shall be adjudged to be
invalid or unconstitutional, such adjudication shall not affect the validity of the Ordinance as a whole or any
section, provision or part thereof not adjudged invalid or unconstitutional.
SECTION IV. EFFECTIVE DATE. This Ordinance shall be in full force, after final passage, approval and
publication, as provided by law.
Passed and approved this day of 2015.
MAYOR
ATTEST:
CITY CLERK
Approved by:
City Attorney's Office
Chapter 11
LICENSINGG
17-11-1: LICENSE REQUIRED:
17-11-2: APPLICATION! FOR LICENSE:
17-11-3: EXAMINATION FEE:
17-11-4: LICENSING STANDARDS:
17-11-5: REEXAMINATIONS:
17-11-9: INACTIVE LICENSE:
17-11-10: PENALTIES FOR VIOLATION:
17-11-1: LICENSE REQUIRED:''
A. Master Electrician: No person shall perform unsupervised electrical work, within Iowa City, with or
without compensation unless the person holds a master electrician's class A license issued by
the state of Iowa.
B. Journeyman Electrician No person shall work as a journeyman electrician within the city unless
the person holds a journeyman electrician's class A license issued by the state of Iowa.
C. Fire Alarm: No person shall work as a fire alarm installer or perform maintenance on fire alarm
systems unless the person holds a fire alarm license issued by the state of Iowa.
D. Fire Sprinkler InstaNer: No person shall work as a fire sprinkler installer or perform maintenance
on fire sprinkler systems unless the person holds a fire sprinkler installer's license issued by the
state of Iowa.
E. Fire Sprinkler Maintenance: No person shall perform maintenance on a fire sprinkler system
unless the person holds a fire sprinkler maintenance license or fire sprinkler installer's license
issued the state of Iowa.
F. Master HVAC: No person shall undertake the planning, layout, supervision, or perform heating,
ventilation, and air conditioning within the city, with or without compensation, unless the person
holds an HVAC master license issued by the state of Iowa.
G. Journeyman HVAC: No person shall work as a journeyman HVAC installer within the city unless
the person holds an HVAC journeyman license issued the state of Iowa.
H. Ducted Air Heating And Cooling Installer: No person shall install heat and cooling ducts as
regulated by chapter 1 of this code with or without compensation unless the person holds an
HVAC master, HVAC journeyman or a ducted air heating and cooling installer's license issued
by the state of Iowa. (Ord. 09-4329, 3-10-2009)
I. Master Hydronics: No person shall plan for, lay out, supervise or perform hydronics work within
the city, with or without compensation, unless the person holds a master hydronics license or a
master HVAC license issued by the state of Iowa.
J. Journeyman Hydronics: No person shall work as a journeyman hydronics installer unless the
person holds a journeyman hydronics or a journeymen HVAC license issued by the state of
Iowa.
K. Master Plumber: No person shall plan for, lay out, supervise or perform plumbing work within the
city, with or without compensation, unless the person holds a master plumber's license issued by
the state of Iowa.
L. Journeyman Plumber: No person shall work as a journeyman plumber within the city unless the
person holds a journeyman plumber's license issued by the state of Iowa.
M. Sanitary Sewer And Water Service Installer: No person shall work as a sanitary sewer and water
service installer within the city unless the person holds a sanitary sewer and water service
installer's license issued by the city or holds a master or journeyman plumbers license issued by
the state of Iowa.
N. Licensed Persons To Be On Site: There shall be a properly licensed person present at all
locations and at all times where work requiring a license is being performed. At least one
licensed person shall be present for every three (3) laborers. Such licensed person must be an
employee of the permit holder.
O. Unlicensed Persons: No person shall knowingly employ or permit an unlicensed person to
perform work within Iowa City if the work is required by this code or the state of Iowa to be
performed by a licensed person
17-11-2: APPLICATION FOR LICENSE:` - 'L-11
Any person required by this chapter to possess a license shall make application to the state of Iowa
or for a sewer and water installer license make application to the City. (Ord. 02-4037, 8-20-2002)
17-11-3: EXAMINATION FEE:''`
The examination fee for persons applying for a sewer and water installer license shall be established
by resolution of city council and shall not be refunded. (Ord. 02-4037, 8-20-2002)
17-11-4: LICENSING STANDARDS: t' L_1
The City shall issue licenses pursuant to the following provisions:
Sanitary Sewer and Water Service Installer: A sanitary sewer and water installer license shall be
issued to every person who successfully passes the examination approved by the board of appeals.
License Fees: The fee for licenses shall be set by resolution of the city council. (Ord. 02-4037, 8-20-
2002; amd. Ord. 06-4246, 12-12-2006, eff. 1-1-2007)
17-11-5: REEXAMINATIONS: -
Any person who fails the sanitary sewer and water service installer examination or the electrical
homeowner's exam must wait a minimum of thirty (30) calendar days before retesting. (Ord. 06-
4246, 12-12-2006, eff. 1-1-2007)
17-11-6: LICENSE RENEWALS:"- ---2
A. License Expiration: Every sewer and water installer license which has not previously been
revoked shall expire on December 31 of each year. Renewal fees and reinstatement fees shall
be as established by resolution of the city council Any license that has expired may be
reinstated within sixty (60) calendar days after the expiration date upon payment of an additional
reinstatement fee. After the expiration of the sixty (60) calendar day period, no license obtained
by municipal testing, shall be renewed except upon reexamination. Licenses obtained by an
approved third party testing agency, shall be renewed for a period of five (5) years with the
submittal of all required documentation and payment of all back renewal fees from the time of the
license expiration. After the five (5) years, no license shall be renewed except upon
reexamination. (Ord. 06-4246, 12-12-2006, eff. 1-1-2007)
B. Employer Identification: At the time of renewal, each licensee shall identify the company the
licensee is currently employed by. (Ord. 02-4037, 8-20-2002)
17-11-7: REVOCATION OF LICENSE:'
A. The administrative authority, with consent of the board of appeals, may revoke any license issued
by the city if the license holder shows incompetency or lack of knowledge, if the license was
obtained by fraud or for continual violation of any sections of this code.
B. Licenses are not transferable The lending, selling, giving, or assigning of any license or the
obtaining of permits thereunder for any other person shall be deemed cause for revocation.
C. Revocation shall occur only after the administrative authority has given the licensee written notice
and an opportunity for an administrative hearing before the board of appeals. (Ord. 02-4037, 8-
20-2002)
17-11-8: REISSUANCE OF LICENSE AFTER REVOCATION:
If a license is revoked for any reason, another license shall not be issued for at least twelve (12)
months after revocation. (Ord. 02-4037, 8-20-2002)
17-11-9: INACTIVE LICENSE:'-'
Any current Sewer and Water Installer license may be classified as inactive upon written request of
the licensee. Once so classified, the license holder is permitted to maintain the license as current but
will not be permitted to obtain an plumbing permit. The license may be reactivated by payment of the
full license fee for that year. The fee for an inactive license shall be set by resolution of city council.
(Ord. 06-4246,12-12-2006, eff. 1-1-2007)
17-11-10: PENALTIES FOR VIOLATION:'?'
The violation of any provision of this chapter is a municipal infraction as provided for in subsection 1-
"" of this code. (Ord. 09-4329, 3-10-2009)